Normally open fire-resisting duct damper with electric drive mechanism.
EAN codeEAN
  • Description
  • Characteristics
  • Downloads
  • Designation key
  • Mounting
  • Dimensions
  • Electric actuators
  • Electrical connection
Description
Description
USE

The fire dampers are intended for automatic closing of process openings and air duct penetrations in intermediate floors, walls and partitions, as well as closing of openings in supply and exhaust ducts of smoke ventilation systems. The dampers of this particular design are not suitable for installation in air ducts and ducts of premises with rated explosion and fire safety category A and B and in flammable and explosive mixture intakes. The BSK2 fire-resisting duct dampers are capable of resisting fire for at least 120 minutes (EI 120) at the temperature of 600 °C.

DESIGN

The BSK2 series dampers are made in the general-purpose industrial version with a minimized variety of hardware components using low-alloy galvanized steel. The damper flap is made of fire-resistant material. The duct installation design results in two mounting flanges on the casing for integration into a ventilation ducts (air ducting) and external configuration of the drive mechanism for easier maintenance. The BSK2...PKP/ BSK2...PVP/ BSK2...PSP dampers are equipped with a hot and cold zone baffle.

CONTROL AND MODIFICATIONS

The BSK2...PKP/ BSK2...PVP/ BSK2...PSP series dampers are equipped with electric actuator with a built-in return spring and a back-up thermal breaker.Setting the damper to operating position (direct fire contact): remotely, via electric actuator. The damper can be set to the operating or protective position either remotely via the control panel or manually using the manual cocking handle which is always included in the standard delivery set of the electric actuator. In case of the remote control panel failure, the back-up thermal breaker interrupts the power supply to the electric actuator and the return spring sets the damper to the operating position. Emergency damper actuation: The damper flap is set to the protective position automatically (damper unaffected by fire). The electric actuator remains energized at all times.In case of an emergency actuation (direct fire contact): the electric actuator equipped with a return spring is de-energized and the damper flap is set to the operating position by means of the spring energy. In case of a power failure not related to fire and its subsequent restoration at the actuator with a return spring, the damper flap returns to protective position.

   
THE BSK2...PKP/BSK2...PVP/BSK2...PSP FIRE SAFETY DAMPER WITH ELECTRIC ACTUATOR AND THERMOELECTRIC BREAKER

Characteristics
Characteristics
Parameter BSK2 40x25/2 .../O O Measurement unit
Air pass 0.084
Weight 20.5 kg
Width 400 mm
Height 250 mm
Mounting Inline -
Documents archieve
Documents archieve
Name
BSK2 - data sheet (pdf 2.01Mb)
BSK2...PKP/ BSK2...PVP/ BSK2...PSP - image (png 570.78Kb)
Designation key
Designation key

Mounting
Mounting

The damper must be installed into the building envelope structure in accordance with the applicable standards and regulations. The seal fire resistance must be at least equal to that of the building envelope. The dampers can be installed in any position in vertical and horizontal ducts of fire-protection structures. The ducts for damper installation must be made in such a way so as to prevent the transfer of loads caused by the fire-protection structures to the damper casing. The adjoining air duct must be suspended in such a way so as to prevent the transfer of air duct load to the damper flange. The minimum free space for accessing the control parts must be at least 350 mm. Make sure to arrange an inspection hole. While carrying out the installation consider size K. When two or more dampers are installed into the same fireprotection separation structure, the distance between the two adjacent dampers must be at least 200 mm.

If such installation is not possible, the damper casing part between the fire-protection separation space and the damper flap must be insulated with a suitable material pursuant to the applicable standards. If such installation is not possible, the damper casing part between the fireprotection separation structure and the damper flap must be insulated with a suitable material pursuant to the applicable standards. The damper casing must not deform any deformation during embedding. After the installation the flap must not catch against the damper casing while opening or closing. The fire safety damper can be integrated into a tight wall structure – e.g. made of conventional concrete work of minimum width W = 100 mm or into a plasterboard wall of the necessary fire resistance class or into a tight ceiling structure – e.g. made of conventional concrete of minimum width W = 150 mm. Do not use any foaming substances for sealing the damper in the separation structure.

INSTALLATION RECOMMENDATIONS FOR BSK2...PKP/ BSK2...PVP/BSK2...PSP FIRE SAFETY DAMPERS WITH AN ELECTRIC ACTUATOR AND THERMOELECTRIC BREAKER
  IN HORIZONTAL BUILDING STRUCTURES

IN VERTICAL BUILDING STRUCTURES DUCT MODIFICATION WITH AN AIR DUCT

Dimensions
Dimensions

Duct cross-section Size [mm] Weight [kg]
B B1 B2 B3 H H1 H2 H3 S
BSK2 40x25/2 .../O O 400 420 440 480 250 270 290 330 540 20.5
Electric actuators
Electric actuators

BELIMO ELECTRIC ACTUATORS WITH A RETURN SPRING AND A THERMAL BREAKER

Parameters Basic models Models with increased torque Models with the highest torque
Rated voltage [V] AC/DC 24 AC 230 AC/DC 24 AC 230 AC/DC 24 AC 230
Rated voltage range [V] AC 19.2…28.8
DC 21.6…28.8
АС 198…264 AC 19.2…28.8
DC 21.6…28.8
АС 198…264 AC 19.2…28.8
DC 21.6…28.8
АС 198…264
Rated voltage frequency AC [Hz] 50/60 50/60 50/60
Power consumption in rest position [W] 0.8 1.1 1.4 2.1 2 3
Power consumption in operation [W] 2.5 3.5 4 5 7 8.5
Maximum design capacity [VA] 4 6.5 6 10 10 11
Motor torque [Nm] 4 9 18
Spring torque [Nm] 3 7 12
SEC class III II III II III II
Ingress protection rating IP54 IP54 IP54 IP54 IP54 IP54
Auxiliary switches 2 pcs., single-pole, reversible, 1 mA…3(0,5)A, AC 250 V 2 pcs., single-pole, reversible, 1 mA…6(3)A, AC 250 V
Electric motor connection cable 1 m, 2 x 0.75 mm² (halogen-free)
Auxiliary switch connection cable 1 m, 6 x 0.75 mm² (halogen-free)
Running time spring 20 seconds at -10…+55 °C
< 60 seconds at -30…-10 °C
20 seconds at -10…+55 °C
< 60 seconds at -30…-10 °C
16 seconds at +20 °C
Running time motor < 60 s/90° < 60 s/90° < 120 s/90°
Response temperature of thermal breaker sensors Duct sensor 72 °C
Outdoor sensor 72 °C
Service life Min. 60 000 emergency positions
Technical maintenance Not required

 

ZERN ELECTRIC ACTUATORS WITH A RETURN SPRING AND A THERMAL BREAKER

Parameters Basic models Models with increased torque
Rated voltage [V] AC/DC 24 AC 100–240 AC/DC 24 AC 100–240
Rated voltage range [V] AC/DC 19.2…28.8 АС 85…265 AC/DC 19.2…28.8 АС 85…265
Rated voltage frequency AC [Hz] 50/60 50/60
Power consumption in rest position [W] 3 3
Power consumption in operation [W] 5 5
Motor torque [Nm] 5 8
Spring torque [Nm] 5 8
SEC class III II III II
Ingress protection rating IP54 IP54 IP54 IP54
Auxiliary switches 2 pcs., single-pole, reversible, 1 mA…3(0,5)A, AC 220 V
Electric motor connection cable 1 m, 2 x 0.5 mm² (halogen-free)
Auxiliary switch connection cable 1 m, 6 x 0.5 mm² (halogen-free)
Running time spring < 20 seconds
< 60 seconds at -30…-10 °С
< 25 seconds
< 60 seconds at -30…-10 °С
Running time motor < 70 s/95° < 100 s/95°
Response temperature of thermal breaker sensors Duct sensor 72 °С
Outdoor sensor 72 °С

 

SIEMENS ELECTRIC ACTUATORS WITH A RETURN SPRING AND A THERMAL BREAKER

Parameters Basic models Models with increased torque Models with the highest torque
Rated voltage [V] AC 24/
DC 24…48
AC 230 AC 24/
DC 24…48
AC 230 AC 24/
DC 24…48
AC 230
Rated voltage range [V] AC/DC ±20 % АС ±15 % AC/DC ±20 % АС ±15 % AC/DC ±20 % АС ±15 %
Rated voltage frequency AC [Hz] 50/60 50/60 50/60
Power consumption in rest position [W] 2 3.5 2 3.5 3 4
Power consumption in operation [W] 3.5 4.5 3.5 4.5 5 6
Maximum design capacity [VA] 5 7 5 7 7 8
Motor torque [Nm] 4 9 18
Spring torque [Nm] 4 7 18
SEC class III II III II III II
Ingress protection rating IP54 IP54 IP54 IP54 IP54 IP54
Auxiliary switches 2 pcs., single-pole, reversible, 6(2)A, AC 24...250 V
Electric motor connection cable 0.9 m, 2 x 0.75 mm² (halogen-free)
Auxiliary switch connection cable 0.9 m, 6 x 0.75 mm² (halogen-free)
Running time spring 15 seconds
< 60 seconds at -30…-10 °С
Running time motor 90 s/90°
Response temperature of thermal breaker sensors Duct sensor 72 °С
Outdoor sensor 72 °С
Service life 10 000 emergency positions
Technical maintenance Not required
Electrical connection
Electrical connection

BASIC MODELS BELIMO AND ZERN ELECTRIC ACTUATORS, BELIMO AND ZERN MODELS WITH INCREASED TORQUE

BELIMO ELECTRIC ACTUATORS WITH THE HIGHEST TORQUE, SIEMENS ELECTRIC ACTUATORS