Blauberg KOMFORT EC DW600-2


Suspended heat recovery air handling unit. Maximum air capacity up to 600 m³/h.
EAN codeEAN4058448021473
  • Description
  • Characteristics
  • Downloads
  • DIMENSIONS
  • Designation key
  • Accessories
Description
Description
FEATURES

Air handling units for efficient supply and exhaust ventilation in flats, houses, cottages and other buildings.Heat recovery minimises ventilation heat losses.Provide controllable air exchange to create the best suitable indoor microclimate.Compatible with round Ø 200 to 400 mm round air ducts.

DESIGN FANS

The casing is made of double-skinned aluzinc panels, internally filled with 20 or 25 mm mineral wool layer for heat and sound insulation.The casing has fixing brackets with vibration absorbing connectors for easy installation.The spigots for connection to the air ducts are located at the side of the unit and are rubber sealed for airtight connection to the air ducts.The service panel ensures easy access to the internals for cleaning, filter replacement and other maintenance operations.

High-efficient external rotor EC motors and centrifugal impellers with backward curved blades are used for air supply and exhaust.EC motors have the best power consumption to air flow ratio and meet the latest demands concerning energy saving and high-efficient ventilation.EC motors are featured with high performance, low noise level and totally controllable speed range.Dynamically balanced impellers.

KOMFORT EC DW600-2 … KOMFORT EC DW1000-4  
KOMFORT EC DW2000-2 … KOMFORT EC DW3800-2  
HEAT RECOVERY AIR FILTRATION

The unit is equipped with a plate cross-flow (KOMFORT EC DW600/1000) or a plate counter-flow (KOMFORT EC DW2000/2800) aluminium heat exchanger for heat recovery. In the unit condensate is collected and drained to the drain pan under the heat exchanger.
The air flows are completely separated in the heat exchanger. Thus smells and contaminants are not transferred from the extract air to the supply air.Heat recovery is based on heat and/or humidity transfer through the heat exchanger plates. In the cold season supply air is heated in the heat exchanger by transferring the heat energy of warm and humid extract air to the cold fresh air. Heat recovery minimizes ventilation heat losses and heating costs respectively.In the warm season the heat exchanger performs reverse and intake air is cooled in the heat exchanger by the cool extract air. That reduces operation load on air conditioners and saves electricity.

FREEZE PROTECTIONThe electronic frost protection system based on bypass and heater is used to prevent the heat exchanger freezing in cold seasons. The bypass damper is opened and the heater is turned on automatically according to the feedback from the temperature sensor. Cold intake air passes by the heat exchanger and is warmed up to set temperature in the heat exchanger. Synchronously extract air that passes by the heat exchanger is used for its defrosting. After a freezing danger is over the bypass damper is closed, the heater is turned off. The unit reverts to the normal operation mode.

The built-in G4 supply filter and G4 extract filter provide air filtration.

CONTROL AND AUTOMATION

The unit incorporates an integrated control system with a wall-mounted control panel and a sensor display.
The standard delivery set includes a 10 m cable for connection of the unit and the control panel.Automation functions:

  • Activating/deactivating the unit.
  • Setting required speed for the supply and extract fan for the unit air flow control. Each speed is individually adjusted during set-up.
  • Set supply air temperature maintaining by means of the circulating pump and heat medium regulating valve control.
  • Water heater freezing protection on feedback from the temperature sensor downstream of the water heating coils and the return water temperature sensor.
  • Pre-heating cycle prior to the heater start and maintaining set return water temperature during the fan shutoff.
  • Opening/closing the bypass damper for summer ventilation.
  • Setting and maintaining room or duct air temperature.
  • Timer activation/deactivation and set-up.
  • Setting day- and week-scheduled operation of the unit.
  • Operation control on feedback from FS1 duct humidity sensor (to be ordered separately) or on the humidity sensor in the control panel.
  • Filter clogging control.
  • System shutdown on signal from the fire alarm panel.
  • Controlling supply and exhaust air dampers (to be ordered separately).
  • Cooler control (to be ordered separately).
AIR HEATER

The unit is equipped with a water (glycol) heater for operation at low outside air temperature.The integrated water heater is activated to warm up supply air flow if set indoor air temperature may not be reached by means of heat recovery only.Heat medium temperature control ensures supply air temperature maintaining.The air temperature sensor downstream of the waterheating coils and the return water temperature sensor are used for freezing protection of the water heater.

MOUNTING

Mounting to the ceiling with fixing brackets.The correct mounted unit must provide free condensate collection and drainage as well as good access for servicing and filter replacement.Servicing access:

  • KOMFORT EC DW600/1000: on the right or left panel side;
  • KOMFORT EC DW2000/3800: on the bottom.
Characteristics
Characteristics
Parameter KOMFORT EC DW600-2 Measurement unit
Number of water coil rows 2 -
Voltage 230 V
Phase 1 ˜
Frequency 50/60 Hz
Current 1.60 A
Power 270 W
RPM 3060 min-1
Air capacity 600 m³/h
Air capacity 167 l/s
Sound pressure level at 3 m distance 53 dBА
EC motor yes -
Temperature of transported air -25…+40 °С
Insulating material 20 mm mineral wool mm
ErP 2016, 2018 -
Extract filter G4 -
Supply filter G4 -
Heat recovery efficiency 90 %
Heat exchanger type counter-flow -
Weight 77 kg
Heat exchanger material aluminum -
Connected air duct diameter 200 mm
Casing material aluzinc -
SEC class A -
Mounting ceiling mounting -
Documents archieve
Documents archieve
Name
KOMFORT ЕС DW - data sheet (pdf 1.47Mb)
KOMFORT ЕС DW - user manual (pdf 7.69Mb)
KOMFORT ЕС DW600/1000 - image (png 378.8Kb)
DIMENSIONS
DIMENSIONS

Model Dimensions [mm]
D B B1 B2 H L L1
KOMFORT EC DW600-2 199 827 711 - 283 1238 1286
Designation key
Designation key
Series Motor type Mounting type Heater type Nominal air flow [m³/h]   Number of water coil rows Service side
KOMFORT EC: electronically commutated motor D: suspended mounting, horizontally oriented spigots W: water heater 600; 1000; 2000; 3800 - 2; 4 L: Left
R: Right
Accessories
Accessories
    KOMFORT EC DW600-2
G4 panel filter   FP 782x128x20 G4
G4 pocket filter FPT 392x236x27 G4
Silencer SD 200
Silencer   SDF 200
Water mixing unit WMG
Backdraft air damper   VRV 200
Air damper VKA 200
Internal humidity sensor   FS1
Electric actuator   LF230