Description
Description
The silencer is used for attenuation of the operation noise generated by ventilation equipment and spreaded in the the air ducts. Designed for connection to round air ducts.   The SDV silencer has a polymer-coated steel casing filled with noncombustible material that has a protective coating to prevent fiber deformation. The silencer has an internal sound-absorbing element to increase sound attenuation efficiency.
Characteristics
Characteristics
Parameter SDV-710-1D SDV-710-1.5D SDV-710-2D Measurement unit
Weight 39.0 55.0 71.0 kg
Documents archieve
Documents archieve
Name
SDV - image (png 118.06Kb)
SDV - data sheet (pdf 316.48Kb)
Modifications
Modification name
SDV-710-1D
SDV-710-1.5D
SDV-710-2D
+
+
+
Dimensions
Dimensions

Model Overall dimensions [mm]
ØD ØD1 ØD2 Md n L
SDV-710-1D 710 770 825 M10 16 712
SDV-710-1.5D 1067
SDV-710-2D 1422
Noise level reduction
Noise level reduction
The values shown in the tables represent the difference between the sound power level (Lw) of the combination of the fan, the attenuator and the power of one fan.   To determine the sound power level of the fan equipped with a silencer, the insertion loss must be subtracted from the rated sound power level (Lw) of the fan on the mid-frequency spectrum in the octave band given in the fan specifications.
Model Sound attenuation by frequency band [dB] LwA [dBA]
Sound-power level, A-weighted
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
SDV-710-1D 5 6 10 18 22 19 15 11 25
SDV-710-1.5D 7 9 13 23 28 25 22 16 31
SDV-710-2D 8 11 16 28 34 31 28 20 37
Pressure drops
Pressure drops
Model Air speed 5 m/s Air speed 10 m/s Air speed 15 m/s
Air flow [m³/h] Pressure drop [Pa] Air flow [m³/h] Pressure drop [Pa] Air flow [m³/h] Pressure drop [Pa]
SRV-710-1D 5300 4 10400 11 15500 25
SRV-710-1.5D 5300 5 10400 14 15500 33
SRV-710-2D 5300 5.5 10400 17 15500 41