Blauberg EVH 150-2.0-1 S21 V.2
Electric duct preheater for heat exchanger freeze protection.
EAN
- Description
- Characteristics
- Capacity diagram
- Downloads
- Designation key
- Compatibility chart
- Dimensions
Description
Description
FEATURES
Heat exchanger freeze protection by means of preheating of the intake air. Maintains the duct air temperature at a point that prevents the heat exchanger freezing. Compatible with Ø 125 up to 315 mm air ducts.
CONTROL
Equipped with a power cable. The signal cable for connection to the controller of the air handling unit. Equipped with a triac power regulator.Regulation is carried out via switching-on and switching-off the full load. Load commutation is carried out by the semiconductor device (triac). The switching unit has no wearing mechanical elements. Equipped with overheat thermostats:
- main protection with automatic restart at +60 °С;
- emergency protection with manual restart at +90 °С.
|
|
DESIGN
The casing is internally filled with 20 mm layer of non-flammable mineral wool. The casing and the junction box are made of galvanized steel. Heating elements are made of stainless steel. Airtight connection to air ducts due to rubber seals.
MOUNTING
Fixation to round air ducts by means of clamp (included in the delivery). The heater is controlled by the air handling unit through the cable supplied and connected to the heater at the factory.In case of horizontal mounting position the control box cover must be directed upwards only. Permitted deviation up to 90°. The control box cover may not be positioned downwards!
|
Characteristics
Characteristics
Parameter |
EVH 150-2.0-1 S21 V.2 |
Measurement unit |
Current |
8.7 |
A |
Power |
2000 |
W |
Min. air flow |
170 |
m³/h |
Min. air flow |
47 |
l/s |
Insulation |
incombustible mineral wool, 20 mm |
mm |
Casing material |
galvanized steel |
-
|
Air duct |
for round air ducts |
-
|
Connection diameter |
150 |
mm |
Capacity diagram
Capacity diagram
Documents archieve
Documents archieve
Designation key
Designation key
Series |
Connected air duct diameter [mm] |
|
Heater power [kW] |
|
Number of phases |
Compatibility with automation |
EVH |
125; 150; 160; 200; 250; 315 |
– |
0.6; 0.8; 1.2; 1.7; 2.0; 3.0 |
– |
1: single-phase |
S21 V.2: compatible with an S21 automation without a DB-9M connector |
Compatibility chart
Compatibility chart
Heater model |
Unit model |
EVH 150 S21 V.2 |
KOMFORT EC SB unit with a ∅ 150 pipe and an S21 automation without a DB-9M connector |
Dimensions
Dimensions
Model |
Overall dimensions [mm] |
Ø D |
B |
H |
L |
L1 |
EVH 150-2.0-1 S21 V.2 |
150 |
189 |
280 |
306 |
192 |