Login
Not registered yet? Take advantages of registration:
Products saving in a binding to the projects
Online consultation from experts
Signup

Privacy policy

Blauberg Iso Box-F 150 ES


Sound-insulated inline centrifugal fans with electrostatic filters. Maximum air flow up to 530 m³/h.
EAN codeEAN
  • Description
  • Characteristics
  • Capacity diagram
  • Downloads
  • Designation key
  • DIMENSIONS
  • Additional characteristics
  • Replaceble filters
Description
Description
USE

Supply ventilation systems installed in premises with high requirements to clean air and the noise level.Suitable for limited mounting space.Compatible with Ø 100 up to 200 mm round air ducts.

DESIGN AIR FILTRATION

The casing is made of polymer-coated steel, internally filled with soundinsulating layer.Internal airtight terminal box for power supply.Easy access for filter maintenance.

G4 filter provides primary filtration.Fine filtering with an electrostatic filter.Quick access to replaceable filters through service panel.

MOTOR ELECTROSTATIC FILTER

Iso Box-F ES series: four-pole asynchronous motor with external rotor and centrifugal impeller with forward curved blades.Iso Box-F ES V2 series: two-speed asynchronous motor with external rotor and centrifugal impeller with forward curved blades.
Equipped with ball bearings for longer service life.Integrated thermal protection with automatic restart.Dynamically balanced turbine.

Electrostatic filter enables purification of air from fine dust and soot, spray, smoke and other particles with the size 0.01 microns and less.Max. filter cleaning efficiency 98 %.The electrostatic filters rely on gravity of oppositely charged objects.The polluted air stream flows through the spray charging unit for the particles ionization.Ionized particles are moved by the airstream and accumulated on the collecting plates which are oppositely charged.
The filter cleaning interval depends on the inlet air pollution density and may vary from 7 up to 21 days.The filter cleaning interval is determined by the visual inspection of the filters.Vacuum cleaning is allowed.

SPEED CONTROL

Iso Box-F ES series: smooth speed control with an external CDT E1.8 thyristor controller (available upon separate order).Iso Box-F ES V2 series: two-speed control with the external CDP-2/10 speed switch (available upon separate order).

MOUNTING

Due to compact design is the ideal solution for mounting in limited spaces, including the space behind false ceiling.Any mounting position.Wall or ceiling mounting with fixing brackets supplied as a standard.

Characteristics
Characteristics
Parameter Iso Box-F 150 ES
50 Hz
Iso Box-F 150 ES
60 Hz
Measurement unit
Voltage 230 230 V
Phase 1 1 ˜
Frequency 50 60 Hz
Current 0.51 0.57 A
Power 112 131 W
RPM 1250 1430 min-1
Maximum air flow 460 530 m³/h
Maximum air flow 128 147 l/s
Sound pressure level at 3 m 25 27 dBА
Transported air temperature -25...+40 -25...+40 °С
Ingress protection rating IPX4 IPX4 -
EC motor yes yes -
Casing material polymer-coated steel polymer-coated steel -
Connection diameter 150 150 mm
Design centrifugal centrifugal -
PM 2.5 Ratio 95.6 95.6 %
SEC class C C -
Weight 18.5 18.5 kg
Mounting ceiling mounting, wall mounting ceiling mounting, wall mounting -
ErP 2018 2018 -
Capacity diagram
Capacity diagram
  • Selection method:
  • Air capacity:
  • Pressure:
Operating point
  • Air capacity: --
  • Pressure: ---
Documents archieve
Documents archieve
Select a document type
  • Catalogues
  • Technical documentation
  • Certificates
Name
Iso Box-F ES (V2) - data sheet (pdf 915.9Kb)
Iso Box-F ES (V2) - image (png 220.46Kb)
Iso Box-F ES (V2) - user manual (pdf 2.05Mb)
Designation key
Designation key
Series Duct diameter [mm] Filters Motor modification Speed
Iso Box-F 100; 150; 200   ES: electrostatic filter  _: standard type
L: low-powered motor
 _: one speed
V2: two-speed
DIMENSIONS
DIMENSIONS

Type Dimensions [mm]
ØD L H B L1 B1 L2 B2
Iso Box-F 150 ES 150 785 300 458 855 551 730 502
Additional characteristics
Additional characteristics
Sound power level, A-weighted Total Octave frequency bands [Hz] LpA 3 m LpA 1 m
63 125 250 500 1000 2000 4000 8000
LwA to inlet [dBA] 53 39 40 47 50 41 40 38 27 33 43
LwA to outlet [dBA] 58 42 39 47 54 50 51 45 35 37 47
LwA to environment [dBA] 46 36 38 39 42 34 28 27 23 25 35
Replaceble filters
Replaceble filters
  Iso Box-F 150 ES
G4 Panel filter FP 270x425x47 G4