Blauberg Iso-K 160 4E
- Description
- Characteristics
- Capacity diagram
- Downloads
- Designation key
- Dimensions
- Additional characteristics
- Accessories
USE
Hot and highly polluted air extract up to +120 °C in high resistance condition. Kitchen placement extract systems (combined with grease filters). Ventilation for baking halls. Welding gas extract. The fans is available for round air ducts Ø 150, 160, 200, 250, 315, 355, 400, 450 mm. DESIGNGalvanized steel casing internally filled with 50 mm thermal- and sound-insulating layer made of non-flammable mineral wool. The fan casing is installed on a supporting mounting frame with integrated vibration isolators. The swivel motor-impeller block is attached to the swivel door which facilitates the fan servicing. |
MOTOR
Single- or three-speed motor. Galvanized steel impeller. Equipped with ball bearings for longer service life. Dynamically balanced impeller. F class motor winding insulation and IP54 ingress protection rating. OPERATION AND SPEED CONTROLSmooth or step-up speed control with an auto transformer or frequency inverter (both available upon separate order). MOUNTINGCompatible with round air ducts. The spigot diameter matches the standard air duct sizes. Mounting to the wall with the mounting angle bracket UM Iso-K. Available upon separate order. External terminal box on the motor for connection to power mains. |
Parameter | Iso-K 160 4Е | Measurement unit |
---|---|---|
Phase | 1 | ˜ |
Voltage | 230 | V |
Frequency | 50 | Hz |
Current | 1.7 | A |
Power | 180 | W |
RPM | 1450 | min-1 |
Maximum air capacity | 700 | m³/h |
Maximum air flow | 194 | l/s |
Sound pressure level at 3 m | 41 | dBА |
Max. operating temperature | -20…+120 | °С |
Motor IP rating | IP54 | - |
Ingress protection rating | IP54 | - |
EC motor | no | - |
Weight | 17.0 | kg |
Casing material | galvanized steel | - |
Outdoor mounting | yes | - |
Sound-insulated casing | yes | - |
Air duct | for round air ducts | - |
Connection diameter | 160 | mm |
Design | centrifugal | - |
Type | Exhaust | - |
Mounting | Inline | - |
- Selection method:
- Air capacity:
- Pressure:
- Air capacity: --
- Pressure: ---
Series | Spigot diameter [mm] | Motor | |
Number of poles | Phase | ||
Iso-K | 150; 160; 200; 250; 315; 355; 400; 450 | 2; 4; 6 | E: single-phase D: three-phase |
Model | Overall dimensions [mm] | |||||||||
Ø D | B | B1 | H | H1 | L | L1 | L2 | L3 | L4 | |
Iso-K 160 4E | 160 | 410 | 330 | 540 | 365 | 525 | 500 | 470 | 475 | 205 |
Sound power level, A-weighted | Total | Octave frequency bands [Hz] | |||||||
63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | ||
LwA to inlet [dBA] | 76 | 68 | 70 | 72 | 62 | 59 | 63 | 57 | 61 |
LwA to outlet [dBA] | 77 | 73 | 77 | 79 | 70 | 66 | 67 | 60 | 53 |
LwA to environment [dBA] | 57 | 51 | 56 | 57 | 50 | 49 | 48 | 40 | 33 |