Blauberg Iso-VK 355 4E
- Description
- Characteristics
- Downloads
- Designation key
- Dimensions
- Accessories
- Modifications and options
USE | MOTOR | |||
Designed to extract contaminated hot air up to 120 °C, containing grease (when using grease filters), in high resistance conditions.Ideally function in various ventilation systems for restaurant or café kitchens, industrial bakeries, removal of gases generated during welding operations.Various application possibilities due to a special transformable casing design.Compatible with ∅ 315 up to 800 mm round or 500x500 up to 1175x1175 mm rectangular air ducts. |
Highly reliable single-phase or three-phase motor with steel high-performance centrifugal impeller with backward curved blades.The motor is maintenance free.Motor insulation winding class – F.Degree of protection – IP55. |
|||
SPEED CONTROL | ||||
DESIGN |
Step speed control with transformer speed controller is available for three-phase motors. MOUNTING The fan is mounted with rectangular or round air ducts.Connected to air ducts with flexible vibration-absorbing connectors or connecting reducers of respective diameters.Power is supplied to the fan through an external terminal box.The fans can be installed in any mounting position with respect to air flow direction in the system. While mounting provide enough servicing space.The direction of air flow can be easily changed by rearranging the panel. |
|||
Casing made of aluminium frame and removable aluzinc thermal- and sound-insulated double-skinned sandwich panels.Casing internally filled with 20 mm non-flammable mineral wool.Position of the removable panels can be adjusted to inline air flow or 90° angle air flow.Due to corrosion-resistant casing and thermal insulation the fan is suitable for external mounting.Motor located outside the airflow and separated from the impeller by a metal panel. |
Parameter | Iso-VK 355 4E | Measurement unit |
---|---|---|
Voltage | 230 | V |
Phase | 1 | ˜ |
Frequency | 50 | Hz |
Power | 370 | W |
Current | 3.3 | A |
RPM | 1452 | min-1 |
Maximum air flow | 889 | l/s |
Maximum air flow | 3200 | m³/h |
Sound pressure level at 3 m | 57 | dBА |
Max. operating temperature | –25…+120 | °С |
Motor IP rating | IP55 | - |
Ingress protection rating | IPX4 | - |
EC motor | no | - |
Casing material | aluzinc | - |
Outdoor mounting | no | - |
Sound-insulated casing | yes | - |
Air duct | for round air ducts | - |
Connection diameter | 355 | mm |
Design | centrifugal | - |
Type | Exhaust | - |
SEC class | – | - |
Weight | 47.4 | kg |
Mounting | Inline | - |
Series | Spigot diameter [mm] | Motor | |
Number of poles | Phase | ||
Iso-VK | 315; 355; 400; 450; 500; 560; 630; 710; 800 | 2; 4; 6 | E: single-phase D: three-phase |
Model | Overall dimensions [mm] | |||||||
H | H1 | H2 | L | L1 | W | W1 | W2 | |
Iso-VK 355 4E | 600 | 638 | 540 | 600 | 638 | 600 | 638 | 225 |
Flexible connector | Mounting bracket | Hood | Round flange | Speed controllers (3 ~ 400 only) |
|
EVA Iso-VK | MH Iso-VK | RSD Iso-VK | FR Iso-VK | CDR5E D… TP | CDR5E D… M |
FLEXIBLE CONNECTOR EVA ISO-VK | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
MOUNTING BRACKET MH ISO-VK | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
HOOD RSD ISO-VK | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
ROUND FLANGE FR ISO-VK | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|