Blauberg KOMFORT Roto EC DE 351-E R S21
Maximum air flow up to 497 m³/h.
- Description
- Characteristics
- Downloads
- Designation key
- Dimensions
- Additional characteristics
- Accessories
FEATURES
Air handling units for efficient supply and exhaust ventilation in flats, houses, cottages and other buildings. Heat recovery is provided by the rotary heat exchanger and minimizes ventilation heat losses. Controllable air exchange for creating the best suitable indoor microclimate. DESIGNThe unit casing is made of painted steel, internally filled with mineral wool layer for heat and sound insulation. The insulation is 40 mm thick. KOMFORT Roto EC D … L – left-handed unit. KOMFORT Roto EC D … R – right-handed unit. HEATERUnits KOMFORT Roto EC DE are equipped with an electric heater. |
AIR FILTRATION
Two built-in Coarse 90% (G4) filters provide efficient supply air filtration. Supply ePM1 65% (F7) filter available as an option. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
KOMFORT ROTO EC D 351 … L | KOMFORT ROTO EC D 351 … R | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
HEAT RECOVERY
The unit has an efficient rotary heat exchanger. The advantages of the rotary heat exchanger as compared to plate heat exchangers include no condensate generation, maintaining comfort air humidity and high freeze resistance. KOMFORT Roto EC D … – equipped with condesing rotor. KOMFORT Roto EC D … -E – equipped with sorption rotor. CONTROL AND AUTOMATIONThe units are equipped with an integrated automation system. The remote control panel is not included in the delivery set (purchased separately). The S21 controller allows to integrate the unit into the Smart Home system or BMS (Building Management System). Unit control is done via Wi-Fi using the mobile application Blauberg Home.
|
AUTOMATION FUNCTIONS
Option: function is available when purchasing the appropriate accessory (see the "Accessories" tab). |
Parameter | KOMFORT Roto EC DE 351-E R S21 | Measurement unit |
---|---|---|
Voltage | 230 | V |
Phase | 1 | ˜ |
Frequency | 50/60 | Hz |
Integrated electric preheater power | 1200 | W |
Max. unit power | 1411 | W |
Max. power without electric heater | 211 | W |
Max. unit current | 6.86 | A |
Electric heater current | 5.32 | A |
Max. unit current without electric heater | 1.54 | A |
Maximum air flow | 497 | m³/h |
Sound pressure level at 3 m | 39 | dBА |
Transported air temperature | -25...+40 | °С |
Insulation | 40 mm mineral wool | mm |
Extract filter | G4 / Coarse > 60 % | - |
Supply filter | G4 / Coarse > 60 % (option: F7 / ePM1 60 %) | - |
Heat recovery efficiency | 85 | % |
EC motor | yes | - |
Heat exchanger type | Sorption | - |
Connected air duct diameter | 200 | mm |
Weight | 82 | kg |
Casing material | painted steel | - |
SEC class | A | - |
Mounting | ceiling mounting, wall mounting | - |
Series | Motor | Casing type | Casing modification | Size (Nominal airflow / 10) | Modification | Heat exchanger type | Unit version | Control system |
KOMFORT Roto | EC: electronically commutated motor | D: vertical | _: w/o heater E: electric reheater |
35: 350 m³/h 65: 650 m³/h |
1: by default | _: Condensing rotor -E: Sorption rotor |
L: left version R: right verstion |
S21 |
Model | Overall dimensions [mm] | |||||||
Ø D | Ø D1 | H | H1 | L | L1 | W | W1 | |
KOMFORT Roto EC DE 351-E R S21 | 200 | 125 | 308 | 106 | 1170 | 387 | 700 | 285 |
|
KOMFORT Roto EC DE 351-E R S21 | ||
G4 panel filter | FP 302x256x48 Coarse 90% G4 | |
F7 panel filter | FP 302x256x48 ePM1 60% F7 | |
LCD control panel | S25 | |
Control panel | S22 | |
Wireless control panel | S22 Wi-Fi | |
Internal humidity sensor | FS2 | |
Internal CO2 sensor | CD-3 | |
CO2 sensor with indication | CD-1 | |
Humidity sensor | HR-S | |
Silencer | SD 200 | |
Air damper | VKA 200 | |
Electric actuator | TF230 |