Frequency converters Basic Drive FC-101
INPUTS AND OUTPUTS
Four PNP or NPN programmable digital inputs, 0-24 V DC. 2 analogue inputs (0-10 V or 0/4-20 mA). 2 analogue outputs (0/4-20 mA). 2 relay outputs. MODBUS RTU (RS 485). BACnet MSTP. FC Protocol. N2 Metasys. FLN Apogee. |
USE
This general-purpose variable frequency drive is designed for regulating the rotation speed of an AC electric motor with a maximum power output of 90 kW.This drive is suitable for both general ventilation and smoke extraction ventilation systems. CERTIFIED FIRE MODEThe fire mode prevents the drive from a self-protecting shut-down.While in this mode the drive continues to perform speed regulation duty for mission-critical fans irrespective of control signals, warnings and alarms which may otherwise force it shut down. FILTERA built-in throttle on the DC link ensures a low harmonic load on the power mains as per the EN 61000-3-12 standard requirements. INSTALLATIONThanks to an ultra-compact design the drive can be easily fitted into a larger unit or panel of an air ventilation system.The casings are rated IP20/Type 1/IP21 (optional) and IP54. |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
FREQUENCY CONVERTER TYPE AND SKU CODE | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
VLT® HVAC Basic frequency converters rated up to 22 kW are fitted with circuit boards with a special class 3C3 protective coating. For frequency converters rated higher than 22 kW this protective coating is optional while, the 3C2 coating is standard. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
VLT® FC 101 HVAC BASIC DRIVE FREQUENCY CONVERTER OPTIONS | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|