Description
Description
FEATURES  

A swirl diffuser balances air parameters throughout the entire space of the treated room by forming vortex air flow.

DESIGN  

The units are made from steel and powder-coated. Angled blades provide high ejector capability.

Specially designed casing with additional side slots for horizontal discharge. Ceiling-mounted with direct air duct connection. 

EFFECTIVE FLOW AREA AND RECOMMENDED SPEEDS

Model EFA [m²] V min, [m/s]  V max, [m/s]  Q min, [m³/h]  Q max, [m³/h] 
DWP2 100  0.0086 2 7 62 217
DWP2 125 0.0118 2 6 85 255
DWP2 150 0.0177 2 6 127 382
DWP2 160 0.0222 2 6 160 480
DWP2 200 0.0358 3 9 387 1031
DWP2 250 0.058 2 6 418 1253
DWP2 315 0.083 2 6 598 1793
TECHNICAL DATA

AIR JET DISTRIBUTION GEOMETRY

The diffuser is shaped to create a bi-directional air jet: the side slots ensure horizontal air discharge while the internal blades fixed at 30-35° (depending on the model) form a vortex air jet in the vertical plane.

  • 0.2 hor. is the maximum range of the air jet in the horizontal plane to the point at which the air jet velocity is 0.2 m/s. 
  • 0.2 vert. is the maximum range of the air jet in the vertical plane to the point at which the air jet velocity is 0.2 m/s. 
NOISE CHARACTERISTICS  

Noise characteristics are calculated using the indices given below.

 
OCTAVE FREQUENCY BAND ADJUSTMENT INDEX FOR SOUND POWER LEVELS  
Kok supply mode Octave frequency band [Hz]
63 125 250 500 1000 2000 4000 8000
DWP2 100 16 12 8 5 -2 -5 -14 -20
DWP2 125 15 13 9 3 -1 -6 -13 -20
DWP2 150/160 14 14 9 -1 -2 -4 -9 -21
DWP2 200 15 12 7 3 4 -7 -8 -18
DWP2 250 18 12 7 3 -3 -8 -10 -19
DWP2 315 18 10 9 -1 -4 -6 -10 -16

INDEX FOR DUCT SOUND POWER ABSORPTION BY DIFFUSER

dL supply mode [dB]  Octave frequency band [Hz]
63 125 250 500 1000 2000 4000 8000
DWP2 100 3 3 2 5 3 4 2 1
DWP2 125 3 4 3 5 4 2 2 2
DWP2 150/160 4 14 4 3 6 3 4 3
DWP2 200 6 4 4 6 4 4 3 3
DWP2 250 5 4 5 7 5 5 4 2
DWP2 315 7 6 5 7 4 6 5 4
NON-ISOMETRIC AIR FLOWS

The value given in the catalogue are true for isothermal jets – i.e. when the jet temperature equals the temperature in the room. Any difference in the jet temperature and room temperature affects the jet geometry. During cold air supply the jet is deflected downwards with a reduction in length. During warm air supply the jet is deflected upwards with an increase in length.

I'0,2= I0,2 * KI0,2

KI0.2hor. is the index of horizontal jet length change
KI0.2vert. is the index of vertical jet length change 