Blauberg RSKE / RSKM

RSKE / RSKM
RSKE / RSKM
zoom

Multi-purpose fire safety smoke dampers.
Model features
  • Description
  • Downloads
  • Designation key
  • Installation recommendations
  • Possible variants
  • Technical data
  • Connection diagrams
  • Dimensions
  • Accessories
Description
Description

RSKENormally closed single louvre fire safety dampers RSKMNormally closed multiple-louvre fire safety dampers
   
USE

The dampers are intended for integration into smoke control systems of buildings and structures of various purpose and designed for extraction of combustion products from the spaces of floor corridors, hallways, air locks etc. The dampers can be used as smoke dampers in emergency smoke exhaust ventilation systems in the event of a fire to support evacuation of people from the building at the initial phase of the fire occurring in any of the building spaces. The RSKE/RSKM multi-purpose fire safety smoke dampers are rated to resist fire for 180 minutes (E 180) at the temperature of 600 °C.

DESIGN

The damper casing is made of galvanised steel 1.5 mm thick. The dampers are available in the wall-mounted or duct-mounted variant which have either one or two attachment flanges.

CONTROL AND MODIFICATIONS

The units are available in two control options (with an electric magnet and with an electric actuator in different configurations):

THE DAMPER WITH AN ELECTRIC MAGNET (220 OR 24 V) The damper opens via a spring when the electric magnet is energized. When the damper reaches the end position, a limit switch opens the circuit disconnecting the electric magnet from the power mains. The electric magnet must not remain energized for more than 2 seconds. The damper is reset to the safety (closed) position manually by means of a handle. The damper equipped with an electric magnet has a special button for testing the unit performance.

THE DAMPER WITH A 230 OR 24 V ELECTRIC ACTUATOR AND A RETURN SPRING The flaps are automatically set to the normal (closed) position when applying voltage to the electric actuator. On a fire alarm signal the electric actuator is de-energized causing its return spring to set the damper to an open position. The electric actuator is equipped with a contact group to signal its end positions. The damper can also be controlled manually and fixed in any position. The unit can be unlocked either manually using a hex wrench or automatically upon power-up.

THE DAMPER WITH WITH A 230 OR 24 V ELECTRIC ACTUATOR AND TWO-WIRE CONTROL The damper flap is set from the "Open" to the "Closed" position by an external command sending the voltage phase from one actuator contact to the other. The electric actuator is equipped with a contact group to signal its end positions. The damper can be controlled manually by means of a hex key.

Note. The RSKM dampers with a height of 300 and 350 mm have one louvre. The main difference between the RSKM and the RSKE dampers with a similar height of 300 and 350 mm is that the method of fastening the flap, which ensures a smaller overhang of the flap beyond the RSKM valve.

MOUNTING

The dampers are not intended for installation in air ducts and ducts of spaces with fire and explosion hazard categories A and in local exhaust systems designed for extraction of flammable and explosive mixtures as well as in systems containing environments more aggressive to plain carbon steels than air or those containing sticky and fibrous materials. Fire safety dampers are only intended for installation in systems subjected to regular cleaning to prevent formation of flammable deposits. The damper must be installed into the building envelope structure in accordance with the applicable standards and regulations. The seal fire resistance must be at least equal to that of the building envelope. When preparing for installation the damper casing should be fitted with wooden spreader bars to prevent deformation, torsional twisting or geometry perturbation of the casing which may result in louvre jamming and, eventually, loss of the damper functionality.

Upon completion of the damper brickwork envelope in the smoke shaft, fire division wall or flooring and complete cure (setting) of the sealing, remove the wooden spreader bars and check the louvre for free and frictionless opening. Ground the damper, connect the electromagnet or electric actuator (depending on the modification) to the automatic fire-fighting system and test the damper actuation.

Documents archieve
Documents archieve
Name
RSKE / RSKM - data sheet (pdf 1.81Mb)
RSKE / RSKM - image (png 443.25Kb)
RSKE - image (png 671.73Kb)
RSKM - image (png 672.56Kb)
Designation key
Designation key

Installation recommendations
Installation recommendations

INSTALLATION RECOMMENDATION FOR THE RSKM DAMPER WITH AN INTERNALLY CONNECTED ACTUATOR

IN VERTICAL BUILDING STRUCTURES IN HORIZONTAL BUILDING STRUCTURES
   
DUCT MODIFICATION WITH AN AIR DUCT

INSTALLATION RECOMMENDATION FOR THE RSKM DAMPER WITH AN EXTERNALLY LOCATED ACTUATOR

IN VERTICAL BUILDING STRUCTURES
   
DUCT MODIFICATION WITH AN AIR DUCT IN HORIZONTAL BUILDING STRUCTURES

INSTALLATION RECOMMENDATION FOR THE RSKE DAMPER WITH AN INTERNALLY CONNECTED ACTUATOR

IN VERTICAL BUILDING STRUCTURES
   
DUCT MODIFICATION WITH AN AIR DUCT IN HORIZONTAL BUILDING STRUCTURES
Possible variants
Possible variants
THE RSKM DAMPER WITH AN INTERNALLY INSTALLED ELECTROMAGNET (220/24 V), SINGLE OR DOUBLE FLANGE

The single flange variant is intended for wall or ceiling mounting irrespective of the dimensional orientation. Upon the test or emergency damper actuation, the louvres can only be manually reset to the initial position.

The double flange variant is intended for duct installation irrespective of the dimensional orientation. Upon the test or emergency damper actuation the louvres can only be manually reset to the initial position.

 
FLOW AREA OF THE RSKM SMOKE EXHAUST DAMPER WITH AN ELECTROMAGNET [M²]
B/H [mm] 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
300 0.06                            
350 0.08 0.10                          
400 0.09 0.11 0.12                        
450 0.10 0.13 0.14 0.16                      
500 0.12 0.14 0.15 0.18 0.20                    
550 0.13 0.16 0.17 0.20 0.23 0.25                  
600 0.15 0.18 0.19 0.22 0.25 0.28 0.31                
650 0.16 0.19 0.20 0.24 0.27 0.30 0.33 0.37              
700 0.17 0.21 0.22 0.26 0.29 0.33 0.36 0.40 0.43            
750 0.19 0.22 0.24 0.28 0.31 0.35 0.39 0.43 0.46 0.48          
800 0.20 0.24 0.26 0.30 0.34 0.38 0.42 0.46 0.50 0.51 0.55        
850 0.21 0.26 0.27 0.31 0.36 0.40 0.44 0.48 0.53 0.54 0.59 0.63      
900 0.23 0.27 0.29 0.33 0.38 0.42 0.47 0.51 0.56 0.58 0.62 0.67 0.71    
950 0.24 0.29 0.31 0.35 0.40 0.45 0.50 0.54 0.59 0.61 0.66 0.71 0.75 0.80  
1000 0.25 0.30 0.32 0.37 0.42 0.47 0.52 0.57 0.62 0.64 0.69 0.74 0.79 0.84 0.89

Note: Select the required BxH cross-section damper according to the completed table cells. Since the damper can be installed in any spatial position, a change of the height and width (B and H values) orientation may enable selection of a damper with the cross-section beyond the completed cell range.

For example, a 700x500 mm damper can be ordered as 500x700 mm.

 

THE RSKM DAMPER WITH AN ELECTRIC ACTUATOR (230 OR 24 V) INSTALLED INSIDE THE DAMPER, SINGLE OR DOUBLE FLANGE

The single flange variant is intended for wall or ceiling mounting irrespective of the dimensional orientation.

The double flange variant is intended for duct installation irrespective of the dimensional orientation. The louvres of dampers equipped with a twoposition electric actuator are set to the "open" or "closed" position by an external actuating signal. After a test or emergency actuation the louvres of dampers equipped with an electric actuator with a return spring can return to the initial position automatically upon feeding the supply voltage.

 
FLOW AREA OF THE RSKM SMOKE EXHAUST DAMPER WITH AN ELECTRIC ACTUATOR INSTALLED INSIDE THE DAMPER [M²]
B/H [mm] 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
300 0.06                            
350 0.08 0.10                          
400 0.09 0.11 0.12                        
450 0.10 0.13 0.14 0.16                      
500 0.12 0.14 0.15 0.18 0.20                    
550 0.13 0.16 0.17 0.20 0.23 0.25                  
600 0.15 0.18 0.19 0.22 0.25 0.28 0.31                
650 0.16 0.19 0.20 0.24 0.27 0.30 0.33 0.37              
700 0.17 0.21 0.22 0.26 0.29 0.33 0.36 0.40 0.43            
750 0.19 0.22 0.24 0.28 0.31 0.35 0.39 0.43 0.46 0.48          
800 0.20 0.24 0.26 0.30 0.34 0.38 0.42 0.46 0.50 0.51 0.55        
850 0.21 0.26 0.27 0.31 0.36 0.40 0.44 0.48 0.53 0.54 0.59 0.63      
900 0.23 0.27 0.29 0.33 0.38 0.42 0.47 0.51 0.56 0.58 0.62 0.67 0.71    
950 0.24 0.29 0.31 0.35 0.40 0.45 0.50 0.54 0.59 0.61 0.66 0.71 0.75 0.80  
1000 0.25 0.30 0.32 0.37 0.42 0.47 0.52 0.57 0.62 0.64 0.69 0.74 0.79 0.84 0.89

Note: Select the required BxH cross-section damper according to the completed table cells. Since the damper can be installed in any spatial position, a change of the height and width (B and H values) orientation may enable selection of a damper with the cross-section beyond the completed cell range.

For example, a 700x500 mm damper can be ordered as 500x700 mm.

 

THE RSKM DAMPER WITH AN ELECTRIC ACTUATOR (230 OR 24 V) INSTALLED OUTSIDE THE DAMPER, SINGLE OR DOUBLE FLANGE

The single flange variant is intended for wall or ceiling mounting irrespective of the dimensional orientation.

The double flange variant is intended for duct installation irrespective of the dimensional orientation. The louvres of dampers equipped with a twoposition electric actuator are set to the "open" or "closed" position by an external actuating signal. After a test or emergency actuation the louvres of dampers equipped with an electric actuator with a return spring can return to the initial position automatically upon feeding the supply voltage.

 
FLOW AREA OF THE RSKM SMOKE EXHAUST DAMPER WITH AN ELECTRIC ACTUATOR INSTALLED INSIDE THE DAMPER [M²]
B/H [mm] 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
300 0.07                            
350 0.09 0.11                          
400 0.10 0.12 0.13                        
450 0.11 0.14 0.15 0.17                      
500 0.13 0.15 0.16 0.19 0.21                    
550 0.14 0.17 0.18 0.21 0.24 0.26                  
600 0.16 0.18 0.20 0.23 0.26 0.29 0.32                
650 0.17 0.20 0.21 0.25 0.28 0.31 0.34 0.38              
700 0.18 0.22 0.23 0.27 0.30 0.34 0.37 0.41 0.44            
750 0.20 0.23 0.25 0.29 0.32 0.36 0.40 0.44 0.47 0.49          
800 0.21 0.25 0.27 0.31 0.35 0.39 0.43 0.47 0.51 0.52 0.56        
850 0.22 0.27 0.28 0.32 0.37 0.41 0.45 0.49 0.54 0.55 0.60 0.64      
900 0.24 0.28 0.30 0.34 0.39 0.43 0.48 0.52 0.57 0.59 0.63 0.68 0.72    
950 0.25 0.30 0.32 0.36 0.41 0.46 0.51 0.55 0.60 0.62 0.67 0.72 0.76 0.81  
1000 0.26 0.31 0.33 0.38 0.43 0.48 0.53 0.58 0.63 0.65 0.70 0.75 0.80 0.85 0.90

Note: Select the required BxH cross-section damper according to the completed table cells. Since the damper can be installed in any spatial position, a change of the height and width (B and H values) orientation may enable selection of a damper with the cross-section beyond the completed cell range.

For example, a 700x500 mm damper can be ordered as 500x700 mm.

 

THE RSKE DAMPER WITH AN INTERNALLY INSTALLED ELECTROMAGNET (220/24 V), SINGLE OR DOUBLE FLANGE

The single flange variant is intended for wall or ceiling installation. The damper must be installed according to the installation guidelines for the RSKE damper with an internal actuator (see page 14). Upon the test or emergency damper actuation, the louvres can only be manually reset to initial position.

The double flange variant is intended for duct installation. Upon the test or emergency damper actuation the louvres can only be manually reset to the initial position.

 
FLOW AREA OF THE RSKE SMOKE EXHAUST DAMPER WITH AN ELECTROMAGNET [M²]
B/H [mm] 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
300 0.06                            
350 0.08 0.10                          
400 0.09 0.11 0.12                        
450 0.10 0.13 0.14 0.16                      
500 0.12 0.14 0.15 0.18 0.20                    
550 0.13 0.16 0.17 0.20 0.23 0.25                  
600 0.15 0.18 0.19 0.22 0.25 0.28 0.31                
650 0.16 0.19 0.20 0.24 0.27 0.30 0.33 0.37              
700 0.17 0.21 0.22 0.26 0.29 0.33 0.36 0.40 0.43            
750 0.19 0.22 0.24 0.28 0.31 0.35 0.39 0.43 0.46 0.48          
800 0.20 0.24 0.26 0.30 0.34 0.38 0.42 0.46 0.50 0.51 0.55        
850 0.21 0.26 0.27 0.31 0.36 0.40 0.44 0.48 0.53 0.54 0.59 0.63      
900 0.23 0.27 0.29 0.33 0.38 0.42 0.47 0.51 0.56 0.58 0.62 0.67 0.71    
950 0.24 0.29 0.31 0.35 0.40 0.45 0.50 0.54 0.59 0.61 0.66 0.71 0.75 0.80  
1000 0.25 0.30 0.32 0.37 0.42 0.47 0.52 0.57 0.62 0.64 0.69 0.74 0.79 0.84 0.89

Note: Select the required BxH cross-section damper according to the completed table cells.

 

THE RSKE DAMPER WITH AN ELECTRIC ACTUATOR (230 OR 24 V) INSTALLED INSIDE THE DAMPER, SINGLE OR DOUBLE FLANGE

The single flange variant is intended for wall or ceiling mounting irrespective of the dimensional orientation.

The double flange variant is intended for duct installation irrespective of the dimensional orientation. The louvres of dampers equipped with a twoposition electric actuator are set to the "open" or "closed" position by an external actuating signal. After a test or emergency actuation the louvres of dampers equipped with an electric actuator with a return spring can return to the initial position automatically upon feeding the supply voltage.

 
FLOW AREA OF THE RSKE SMOKE EXHAUST DAMPER WITH AN ELECTRIC ACTUATOR INSTALLED INSIDE THE DAMPER [M²]
B/H [mm] 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
300 0.06                            
350 0.08 0.10                          
400 0.09 0.11 0.12                        
450 0.10 0.13 0.14 0.16                      
500 0.12 0.14 0.15 0.18 0.20                    
550 0.13 0.16 0.17 0.20 0.23 0.25                  
600 0.15 0.18 0.19 0.22 0.25 0.28 0.31                
650 0.16 0.19 0.20 0.24 0.27 0.30 0.33 0.37              
700 0.17 0.21 0.22 0.26 0.29 0.33 0.36 0.40 0.43            
750 0.19 0.22 0.24 0.28 0.31 0.35 0.39 0.43 0.46 0.48          
800 0.20 0.24 0.26 0.30 0.34 0.38 0.42 0.46 0.50 0.51 0.55        
850 0.21 0.26 0.27 0.31 0.36 0.40 0.44 0.48 0.53 0.54 0.59 0.63      
900 0.23 0.27 0.29 0.33 0.38 0.42 0.47 0.51 0.56 0.58 0.62 0.67 0.71    
950 0.24 0.29 0.31 0.35 0.40 0.45 0.50 0.54 0.59 0.61 0.66 0.71 0.75 0.80  
1000 0.25 0.30 0.32 0.37 0.42 0.47 0.52 0.57 0.62 0.64 0.69 0.74 0.79 0.84 0.89

Note: Select the required BxH cross-section damper according to the completed table cells. Since the damper can be installed in any spatial position, a change of the height and width (B and H values) orientation may enable selection of a damper with the cross-section beyond the completed cell range.

For example, a 700x500 mm damper can be ordered as 500x700 mm.

 

THE RSKE DAMPER WITH AN ELECTRIC ACTUATOR (230 OR 24 V) INSTALLED OUTSIDE THE DAMPER, SINGLE OR DOUBLE FLANGE:

The single flange variant is intended for wall or ceiling mounting irrespective of the dimensional orientation.

The double flange variant is intended for duct installation irrespective of the dimensional orientation. The louvres of dampers equipped with a twoposition electric actuator are set to the "open" or "closed" position by an external actuating signal. After a test or emergency actuation the louvres of dampers equipped with an electric actuator with a return spring can return to the initial position automatically upon feeding the supply voltage.

 
FLOW AREA OF THE RSKE SMOKE EXHAUST DAMPER WITH AN ELECTRIC ACTUATOR INSTALLED OUTSIDE THE DAMPER [M²]
B/H [mm] 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
300 0.07                            
350 0.09 0.11                          
400 0.10 0.12 0.13                        
450 0.11 0.14 0.15 0.17                      
500 0.13 0.15 0.16 0.19 0.21                    
550 0.14 0.17 0.18 0.21 0.24 0.26                  
600 0.16 0.18 0.20 0.23 0.26 0.29 0.32                
650 0.17 0.20 0.21 0.25 0.28 0.31 0.34 0.38              
700 0.18 0.22 0.23 0.27 0.30 0.34 0.37 0.41 0.44            
750 0.20 0.23 0.25 0.29 0.32 0.36 0.40 0.44 0.47 0.49          
800 0.21 0.25 0.27 0.31 0.35 0.39 0.43 0.47 0.51 0.52 0.56        
850 0.22 0.27 0.28 0.32 0.37 0.41 0.45 0.49 0.54 0.55 0.60 0.64      
900 0.24 0.28 0.30 0.34 0.39 0.43 0.48 0.52 0.57 0.59 0.63 0.68 0.72    
950 0.25 0.30 0.32 0.36 0.41 0.46 0.51 0.55 0.60 0.62 0.67 0.72 0.76 0.81  
1000 0.26 0.31 0.33 0.38 0.43 0.48 0.53 0.58 0.63 0.65 0.70 0.75 0.80 0.85 0.90

Note: Select the required BxH cross-section damper according to the completed table cells. Since the damper can be installed in any spatial position, a change of the height and width (B and H values) orientation may enable selection of a damper with the cross-section beyond the completed cell range.

For example, a 700x500 mm damper can be ordered as 500x700 mm.

Technical data
Technical data

ELECTROMAGNET

Parameters Parameter value
Rated voltage [V] 220/24
Rated current at the ambient temperature of 25±10 °C [A] 0.6/5.5
Armature stroke [mm] 10±1
Armature release time [seconds] 2
Tractive force [N] 45
Maximum active power consumption at 220 V [W] 600
Maximum total power consumption at 220 V [W] 1200
Maximum total power consumption at 24 V [W] 60

 

BELIMO ELECTRIC ACTUATORS WITH A RETURN SPRING

Parameters Basic models Models with increased torque
Rated voltage [V] AC/DC 24 AC 230 AC/DC 24 AC 230
Rated voltage range [V] AC 19.2…28.8
DC 21.6…28.8
АС 198…264 AC 19.2…28.8
DC 21.6…28.8
АС 198…264
Rated voltage frequency AC [Hz] 50/60 50/60
Power consumption in rest position [W] 1.4 2.0 2 3
Power consumption in operation [W] 4.0 4.5 7 8.5
Maximum design capacity [VA] 6 9.0 10 11
Motor torque [Nm] 9 18
Spring torque [Nm] 7 12
SEC class III II III II
Ingress protection rating IP54 IP54 IP54 IP54
Auxiliary switches 2 pcs., single-pole, reversible, 1 mA…3(0.5)A, AC 250 V 2 pcs., single-pole, reversible, 1 mA…6(3)A, AC 250 V
Electric motor connection cable 1 m, 2 x 0.75 mm² (halogen-free)
Auxiliary switch connection cable 1 m, 6 x 0.75 mm² (halogen-free)
Running time spring 20 seconds at -10…+55 °C
< 60 seconds at -30…-10 °C
16 seconds at +20 °C
Running time motor < 60 s/90° < 120 s/90°
Service life Min. 60 000 emergency positions
Technical maintenance Not required

 

BELIMO TWO-POSITION ELECTRIC ACTUATORS

Parameters Basic models Models with increased torque
Rated voltage [V] AC/DC 24 AC 230 AC/DC 24 AC 230
Rated voltage range [V] AC 19.2…28.8
DC 21.6…28.8
АС 198…264 AC 19.2…28.8
DC 21.6…28.8
АС 198…264
Rated voltage frequency AC [Hz] 50/60 50/60
Power consumption in rest position [W] <0.5 <1 0.5 0.5
Power consumption in operation [W] 7,5 5 12 8
Maximum design capacity [VA] 9 12 18 15
Motor torque [Nm] 15 40
Spring torque [Nm] 20 50
SEC class III II III II
Ingress protection rating IP54 IP54 IP54 IP54
Auxiliary switches 2 pcs., single-pole, reversible, 1 mA…3(0.5)A, AC 250 V
Electric motor connection cable 1 m, 3 x 0.75 mm² (halogen-free)
Auxiliary switch connection cable 1 m, 6 x 0.75 mm² (halogen-free)
Running time < 30 s/90° < 60 s/90°
Service life Min. 10 000 emergency positions
Technical maintenance Not required

 

ZERN ELECTRIC ACTUATORS WITH A RETURN SPRING

Parameters Basic models Models with increased torque
Rated voltage [V] AC/DC 24 AC 100–240 AC/DC 24 AC 100–240
Rated voltage range [V] AC/DC 19.2…28.8 АС 85…265 AC/DC 19.2…28.8 АС 85…265
Rated voltage frequency AC [Hz] 50/60 50/60
Power consumption in rest position [W] 3 3
Power consumption in operation [W] 5 5
Motor torque [Nm] 5 8
Spring torque [Nm] 5 8
SEC class III II III II
Ingress protection rating IP54 IP54 IP54 IP54
Auxiliary switches 2 pcs., single-pole, reversible, 1 mA…3(0.5)A, AC 220 B1 mA…3(0.5)A, AC 220 V
Electric motor connection cable 1 m, 2 x 0.5 mm² (halogen-free)
Auxiliary switch connection cable 1 m, 6 x 0.5 mm² (halogen-free)
Running time spring <20 seconds
< 60 seconds at -30…-10 °С
<25 seconds
< 60 seconds at -30…-10 °С
Running time motor < 70 s/95° < 100 s/95°

 

SIEMENS ELECTRIC ACTUATORS WITH A RETURN SPRING

Parameters Basic models Models with increased torque
Rated voltage [V] AC 24/
DC 24…48
AC 230 AC 24/
DC 24…48
AC 230
Rated voltage range [V] AC/DC ±20 % АС ±15 % AC/DC ±20 % АС ±15 %
Rated voltage frequency AC [Hz] 50/60 50/60
Power consumption in rest position [W] 2 3.5 3 4
Power consumption in operation [W] 3.5 4.5 5 6
Maximum design capacity [VA] 5 7 7 8
Motor torque [Nm] 9 18
Spring torque [Nm] 7 18
SEC class III II III II
Ingress protection rating IP54 IP54 IP54 IP54
Auxiliary switches 2 pcs., single-pole, reversible, 6(2)A, AC 24...250 V
Electric motor connection cable 0.9 m, 2 x 0.75 mm² (halogen-free)
Auxiliary switch connection cable 0.9 m, 6 x 0.75 mm² (halogen-free)
Running time spring 15 seconds
< 60 seconds at -30…-10 °С
Running time motor 90 s/90° 90 s/90°
Service life 10 000 emergency positions
Technical maintenance Not required

Note. The table "Main technical specifications of Siemens two-position electric actuators" is in development. This information is available upon request.

Connection diagrams
Connection diagrams

RSKE/RSKM DAMPER EQUIPPED WITH AN ELECTROMAGNET

SQ1: end switch YA1: electromagnet SB1: damper louvre opening button РК: contact of automatic fire suppression block SA1: power supply circuit disconnection switch of the electromagnetic latch Х1: terminal block

 

1: supply voltage phase 2: contact of automatic fire suppression block 3: supply voltage neutral 4, 5: command circuit control 6, 7: louvre position control 8: grounding bus

 

RSKE/RSKM DAMPER EQUIPPED WITH AN ELECTRIC ACTUATOR

1: "Neutral" contact of supply voltage 2: "Line" contact of supply voltage – closing the damper louvres S1…S6: fixed microswitch contacts for signalling end positions 1: "Neutral" contact of supply voltage 2, 3: "Line" contact of supply voltage damper louvre closing or opening S1…S6: fixed microswitch contacts for signalling end positions
Dimensions
Dimensions

OVERALL AND CONNECTING DIMENSIONS OF RSKM MULTI-LOUVRE DAMPERS

Standard damper size [cm] Minimum flow area [m²] Size [mm] Maximum RSKM weight [kg]
H H1 H2 B B1 B2 L
40х40 0.12 400 420 440 400 420 440 298 9.5
50х50 0.2 500 520 540 500 520 540 297 12.1
60х60 0.31 600 630 660 600 630 660 348 17
70х70 0.43 700 730 760 700 730 760 398 20.3
80x80 0.55 800 830 860 800 830 860 448 24.1
90x90 0.71 900 930 960 900 930 960 498 27.4
100х100 0.9 1000 1030 1060 1000 1030 1060 548 31.7
The RSKM damper with an internally installed electromagnet (220/24 V), single or double flange.
 
 
The RSKM damper with an electric actuator (230 or 24 V) installed inside the damper, single or double flange.
 
 
The RSKM damper with an electric actuator (230 or 24 V) installed outside the damper, single or double flange.

 

OVERALL AND CONNECTING DIMENSIONS OF THE RSKE SINGLE-LOUVRE DAMPER

Standard damper size [cm] Minimum flow area [m²] Size [mm] Maximum RSKE weight [kg]
H H1 H2 B B1 B2 L
40х40 0.12 400 430 460 400 430 460 470 8.2
50х50 0.2 500 530 560 500 530 560 570 10.6
60х60 0.31 600 630 660 600 630 660 670 13.2
70х70 0.43 700 730 760 700 730 760 770 16
80x80 0.55 800 830 860 800 830 860 870 19
90x90 0.71 900 930 960 900 930 960 970 22.2
100х100 0.9 1000 1030 1060 1000 1030 1060 1070 25.6
The RSKE damper with an internally installed electromagnet (220/24 V), single or double flange.
 
 
The RSKE damper with an electric actuator (230 or 24 V) installed outside the damper, single or double flange.
 
 
The RSKE damper with an electric actuator (230 or 24 V) installed inside the damper, single or double flange.
Accessories
Accessories
VANDAL-PROOF MESH

The RSKE/RSKM dampers can be equipped with a vandal-proof mesh.

ALUMINIUM DECORATIVE GRILLE

The unit can be equipped with a decorative grille made of aluminium for a more aesthetic appearance. The grille has a single horizontal row of non-adjustable air flow guides fixed at 45 degrees. The grille is polymer coated and anodised for extra protection against the weather elements. To enable the decorative grille installation, the damper must be embedded at least 40 mm deep into the wall as measured from the wall face to the damper flange. NOTE: While selecting the aluminium decorative grille mind the wall opening dimensions.

CROSS-SECTION DIMENSIONS AND AREA [M²]

B/H [mm] 100 150 200 250 300 350 400 450 500 600 700 800 900 1000
100 0.004 0.007 0.010 0.012 0.015 0.018 0.021 0.024 0.027 0.033 0.039 0.045 0.051 0.057
150 0.070 0.010 0.015 0.018 0.023 0.027 0.031 0.035 0.039 0.047 0.055 0.064 0.072 0.080
200 0.010 0.015 0.021 0.026 0.033 0.038 0.045 0.051 0.058 0.070 0.081 0.093 0.105 0.115
250 0.012 0.018 0.026 0.032 0.041 0.047 0.055 0.062 0.070 0.084 0.098 0.106 0.113 0.128
300 0.015 0.023 0.033 0.041 0.051 0.059 0.069 0.077 0.086 0.096 0.115 0.132 0.149 0.168
350 0.017 0.026 0.038 0.047 0.059 0.068 0.080 0.090 0.099 0.111 0.132 0.151 0.170 0.193
400 0.020 0.030 0.044 0.054 0.069 0.079 0.093 0.103 0.117 0.142 0.166 0.189 0.212 0.237
450 0.023 0.035 0.051 0.062 0.080 0.090 0.107 0.117 0.131 0.160 0.186 0.214 0.239 0.265
500 0.026 0.039 0.056 0.070 0.089 0.100 0.119 0.130 0.145 0.178 0.206 0.238 0.265 0.293
600 0.031 0.047 0.067 0.084 0.105 0.121 0.142 0.158 0.173 0.214 0.246 0.287 0.318 0.349
700 0.036 0.055 0.078 0.094 0.124 0.145 0.170 0.184 0.203 0.251 0.288 0.336 0.372 0.408
800 0.042 0.063 0.090 0.112 0.141 0.163 0.190 0.211 0.232 0.288 0.330 0.385 0.426 0.467
900 0.048 0.072 0.103 0.129 0.160 0.185 0.228 0.238 0.262 0.325 0.372 0.435 0.481 0.527
1000 0.053 0.079 0.113 0.141 0.177 0.204 0.239 0.266 0.292 0.361 0.414 0.484 0.536 0.587

RD, RD1 SMOKE EXHAUST GRILLES

The RSKE/RSKM dampers can be additionally equipped with a smoke exhaust grille. The smoke exhaust grille is used when it is necessary to entirely hide the damper internals from view and if there are no strict requirements to external design. The smoke exhaust grille also doubles as unauthorized access protection for the damper and its actuator. The grille has a single horizontal row of non-adjustable air flow guides fixed at 45 degrees. The grille can be made of galvanized steel (Ts), carbon steel with a special coating (M), stainless steel (N) or aluminium (A). The grille is attached directly to the damper flange by means of self-tapping screws with the flaps facing outward and does not require any additional recessing of the damper.
 
RD SMOKE EXHAUST GRILLE
 
RD1 SMOKE EXHAUST GRILLE

CROSS-SECTION DIMENSIONS AND AREA [M²]

B/H [mm] 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
300 0.059                            
350 0.069 0.079                          
400 0.080 0.091 0.114                        
450 0.090 0.103 0.129 0.142                      
500 0.101 0.115 0.144 0.158 0.173                    
550 0.111 0.127 0.159 0.175 0.191 0.207                  
600 0.122 0.139 0.174 0.191 0.209 0.226 0.244                
650 0.132 0.151 0.189 0.208 0.227 0.246 0.265 0.284              
700 0.143 0.163 0.204 0.224 0.245 0.265 0.286 0.306 0.347            
750 0.153 0.175 0.219 0.241 0.263 0.285 0.307 0.329 0.372 0.394          
800 0.164 0.187 0.234 0.257 0.281 0.304 0.328 0.351 0.398 0.421 0.445        
850 0.174 0.199 0.249 0.274 0.299 0.324 0.349 0.374 0.423 0.448 0.473 0.498      
900 0.185 0.211 0.264 0.290 0.317 0.343 0.370 0.396 0.449 0.475 0.502 0.528 0.554    
950 0.195 0.223 0.279 0.307 0.335 0.363 0.391 0.419 0.474 0.502 0.530 0.558 0.586 0.614  
1000 0.206 0.235 0.294 0.323 0.353 0.382 0.412 0.441 0.500 0.529 0.559 0.588 0.617 0.647 0.676

DESIGNATION KEY