USE For controlling air dampers with cross section up to 1 m2 installed in various ventilation and air conditioning systems. CONTROL Switching on/off by the control knob. The air flow control damper can be controlled by means of the threepoint or open-close controlling. |
DESIGN
The electric actuator is provided with a 5 Nm actuating torque and an overload protection. The actuator is installed directly on the air damper shaft. The angle of rotation is adjusted by mechanical end stops. |
Characteristics
Characteristics
Parameter | BELIMO LM230A | Measurement unit |
---|---|---|
Mechanical control | self-resetting button | - |
Feedback potentiometer | integrated 5 kOhm ± 5 % | - |
Voltage | 230 | V |
Frequency | 50/60 | Hz |
Nominal voltage range | 85...265 ~ | V |
Rated power | 4 | VA |
Power | 1.5 | W |
Connecting cable | 1 m long, 3 x 0.75 mm2 | - |
Sound pressure level | 35 | dBА |
Direction of rotation | selected by 0/1 switch positioning | - |
Torque | 5 (at nominal voltage) | Nm |
Angle of rotation | max. 95°, adjustable with mechanical end stops | - |
Electrical protection class | III low voltage, II totally insulated | - |
Operation temperature | -30…+50 | °С |
Swing time | 150 | sec |
Position indication | mechanical | - |
Storage temperature | -40…+80 | °С |
Ingress protection rating | IP54 | - |
Ambient humidity | 95 %, no condensation | % |
Maintenance | not required | - |
Weight | 0.6 | kg |