Blauberg Centro-M EC 150
- Description
- Characteristics
- Downloads
- Designation key
- Dimensions
- Additional characteristics
- Accessories
USE
Supply and extract ventilation systems installed in various premises. Direct mounting inside air ductworks. For arranging energy-saving and controllable ventilation systems. Compatible with Ø 100 to 400 mm round air ducts. DESIGNThe casing is made of steel with a special polymer coating. Aerodynamically shaped casing. External terminal box for connection to power mains. MOTORHigh-efficient direct current EC motor with external rotor and backward curved blades. EC technology meets the up-to-date requirements to energy-saving and controllable ventilation and provides up to 35 % energy saving as compared to asynchronous motors. EC motor ensures totally controllable speed range for the fan and has integrated overheating protection with automatic restart. EC motor has no friction and wearing parts as capacitor und brushes. Instead a maintenance-free EC controller electronic circuit board is used. The impeller is dynamically balanced. The fan is compatible with 50 Hz and 60 Hz power mains and the maximum speed does not depend on power mains frequency. |
OPERATION AND SPEED CONTROL
The fan speed is controlled with a 0–10 V control signal from the following sources:
The control signal value changes depending on air temperature, pressure, smoke concentration and other parameters. During signal value change the fan with EC motor correspondingly changes the rotations speed and delivers required air volume to the ventilation system. The computer central building management systems (BMS) enable integration of several EC motors in network and precise individual operation control for each fan. MOUNTINGAny mounting position. The fans with the connecting diameter from 100 up to 315 mm are fixed to wall or ceiling with mounting brackets supplied as a standard. The fans with the connecting diameter 355 and 400 mm are fixed with mounting brackets fixed on the casing. Flexible air ducts are fixed on the fan spigots with clamps.
|
Parameter | Centro-M EC 150 | Measurement unit |
---|---|---|
Voltage | 230 | V |
Phase | 1 | ˜ |
Frequency | 50/60 | Hz |
Power | 107 | W |
Current | 0.89 | A |
RPM | 3060 | min-1 |
Maximum air flow | 194 | l/s |
Maximum air flow | 700 | m³/h |
Sound pressure level at 3 m | 48 | dBА |
Transported air temperature | -25...+60 | °С |
Ingress protection rating | IPX4 | - |
EC motor | yes | - |
Weight | 4.70 | kg |
Casing material | polymer-coated steel | - |
Outdoor mounting | no | - |
Sound-insulated casing | no | - |
Air duct | for round air ducts | - |
Connection diameter | 150 | mm |
Design | centrifugal | - |
Type | Exhaust, Supply | - |
SEC class | B | - |
Mounting | Inline | - |
ErP | 2018 | - |
Series | Motor type | Duct diameter [mm] | Options |
Centro-M | EC: electronically commutated motor | 100; 125; 150; 160; 200; 250; 315; 355; 400 | max: high-powered motor FR1: smooth speed controller adjustable from 0 to 100 % and power cable with mains plug G1: speed controller, temperature controller with external temperature sensor, power cable with mains plug W1: power cable with mains plug |
Model | Overall dimensions [mm] | |||||||
∅ D | ∅ D1 | B | B1 | L | L1 | L2 | L3 | |
Centro-M EC 150 | 149 | 305 | 360 | 320 | 240 | 25 | 25 | 30 |
To comply with ErP 2018 it is necessary to use a speed controller and local demand control typology (connect the sensor).
Sound power level, A-weighted | Total | Octave frequency bands [Hz] | LpA 3 m | LpA 1 m | |||||||
63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | ||||
LwA to inlet [dBA] | 89 | 52 | 86 | 85 | 74 | 72 | 70 | 67 | 54 | 68 | 78 |
LwA to outlet [dBA] | 87 | 51 | 85 | 82 | 70 | 68 | 64 | 63 | 51 | 66 | 76 |