Login
Not registered yet? Take advantages of registration:
Products saving in a binding to the projects
Online consultation from experts
Signup

Privacy policy

Blauberg EKH 200-3.4


Duct electrical heater for round ducts.
EAN codeEAN4058448038143
  • Description
  • Characteristics
  • Downloads
  • Designation key
  • Dimensions
  • Additional characteristics
Description
Description
FEATURES

For warming up of supply air in heating, ventilation and air conditioning systems installed in various premises. Compatible with Ø 100 to 315 mm round air ducts.

DESIGN

The casing, the junction box are made of galvanized steel.
Heating elements made of stainless steel. Airtight connection with air ducts due to rubber seals. Several power options for each standard size. For higher heating capacity several heaters may be installed in series. Equipped with overheat protection thermostats:

  • basic protection with automatic restart at +50 °C;
  • emergency protection with manual restart at +90 °C.
  MOUNTING

Fixing to round ducts with clamps. Any mounting position except for the junction box downwards to prevent condensate leakage and short circuit. Install a filter upstream to the heater to protect heating elements against dirt ingress. Recommended distance between the heater and other system components must be not less than two connecting diameters for air flow stabilization. Duct heaters are rated for minimum air flow speed 1.5 m/s and maximum air temperature supplied to the units 40 °C. In case of speed regulation with a speed controller the minimum air speed through the heater must be provided. For correct and safe heater operation an automatic control and protection system is recommended including the following functions:

  • regulation of the heating capacity and temperature of the air heated up;
  • filter clogging control by a differential air pressure sensor;
  • power cut-off in case of supply fan shutdown or low air flow speed as well as in case of actuating the overheat protection thermostats;
  • heat removal from the heating elements after ventilation system shutdown.
Characteristics
Characteristics
Parameter EKH 200-3.4 Measurement unit
Voltage 230 V
Phase 1 ˜
Current 14.8 A
Power 3400 W
Min. air flow 250 m³/h
Min. air flow 69 l/s
Number of heating coils x capacity 2х1700 W
Weight 3.3 kg
Casing material galvanized steel -
Air duct for round air ducts -
Connection diameter 200 mm
Documents archieve
Documents archieve
Select a document type
  • Catalogues
  • Technical documentation
  • Certificates
Name
ЕКН (round) - data sheet (pdf 466.93Kb)
ЕКН (round) - user's manual (pdf 1.16Mb)
ЕКН (round) - image (png 626.13Kb)
Designation key
Designation key
Series Connected air duct diameter [mm]   Heater power [kW]
EKH 100; 125; 150; 160; 200; 250; 315 0.6; 0.8; 1.2; 1.6; 1.8; 2.4; 3.0; 3.4; 3.6; 5.1; 6.0; 9.0
Dimensions
Dimensions

Model Overall dimensions [mm]
D B H L L1
EKH 200-3.4 199 150 302 294 214
Additional characteristics
Additional characteristics
CAPACITY DIAGRAM
 
 
AIR TEMPERATURE INCREASE AS A FUNCTION OF AIR FLOW
 
Similar products