Blauberg EKH 250-3.6
- Description
- Characteristics
- Downloads
- Designation key
- Dimensions
- Additional characteristics
FEATURES
For warming up of supply air in heating, ventilation and air conditioning systems installed in various premises. Compatible with Ø 100 to 315 mm round air ducts. DESIGNThe casing, the junction box are made of galvanized steel.
|
MOUNTING
Fixing to round ducts with clamps. Any mounting position except for the junction box downwards to prevent condensate leakage and short circuit. Install a filter upstream to the heater to protect heating elements against dirt ingress. Recommended distance between the heater and other system components must be not less than two connecting diameters for air flow stabilization. Duct heaters are rated for minimum air flow speed 1.5 m/s and maximum air temperature supplied to the units 40 °C. In case of speed regulation with a speed controller the minimum air speed through the heater must be provided. For correct and safe heater operation an automatic control and protection system is recommended including the following functions:
|
Parameter | EKH 250-3.6 | Measurement unit |
---|---|---|
Voltage | 400 | V |
Phase | 3 | ˜ |
Current | 5.2 | A |
Power | 3600 | W |
Min. air flow | 375 | m³/h |
Min. air flow | 104 | l/s |
Number of heating coils x capacity | 3x1200 | W |
Weight | 2.9 | kg |
Casing material | galvanized steel | - |
Air duct | for round air ducts | - |
Connection diameter | 250 | mm |
Series | Connected air duct diameter [mm] | Heater power [kW] | |
EKH | 100; 125; 150; 160; 200; 250; 315 | – | 0.6; 0.8; 1.2; 1.6; 1.8; 2.4; 3.0; 3.4; 3.6; 5.1; 6.0; 9.0 |
Model | Overall dimensions [mm] | ||||
D | B | H | L | L1 | |
EKH 250-3.6 | 249 | 150 | 356 | 376 | 296 |
CAPACITY DIAGRAM |
AIR TEMPERATURE INCREASE AS A FUNCTION OF AIR FLOW |