Login
Not registered yet? Take advantages of registration:
Products saving in a binding to the projects
Online consultation from experts
Signup

Privacy policy

Blauberg Freshbox E-200 ERV WiFi


Single-room air handling units. Maximum air capacity up to 200 m³/h.
EAN codeEAN4058448051296
  • Description
  • Characteristics
  • Capacity diagram
  • Downloads
  • Designation key
  • Dimensions
  • Accessories
Description
Description
FEATURES

Efficient solution for supply and exhaust ventilation of enclosed spaces.EC fans with low energy consumption.Supply air cleaning is provided by the G4 and F7 filters. Additional air purification due to recirculation. H13 filter is available as an option.Upgradeable with an exhaust duct to provide air extraction from the bathroom.Easy installation.Compact size.Controlled by Android or iOS smartphone or tablet over Wi-Fi.

DESIGN MOTORS

The casing is made of polymer coated steel plates.The front panel provides convenient access for filter maintenance and has a lock for extra security.The unit has two Ø 100 mm pipes for fresh air intake and stale air extraction outside. The third Ø 100 mm pipe (included in the scope of delivery) can be additionally fitted to the unit to connect the exhaust air duct from the bathroom.Available modifications with an integrated preheater and reheater for cold climate applications.

The units feature efficient electronically commutated (EC) motors with an external rotor and impellers with forward curved blades. These stateofthe-art motors are the most advanced solution in energy efficiency today.EC motors are characterised with high performance and optimum control across the entire speed range. In addition to that the efficiency of electronically commutated motors reaches very impressive levels of up to 90 %.

AIR DAMPERS OPERATING PRINCIPLE

The unit is equipped with supply and exhaust air dampers which activate automatically to prevent drafts while the unit is off.

HEAT RECOVERY OPERATION MODE

  • The cold outdoor air passes through the filters and the heat exchanger and then is delivered to the serviced space by the supply centrifugal fan.
  • Warm stale air from indoors passes through the filter and the heat exchanger and is discharged outdoors by the centrifugal fan.
  • The supply and exhaust air flows are fully separated which helps eliminate the possibility of odour or microbial transfer between the streams.
RECIRCULATION OPERATION MODE
  • The supply and exhaust air dampers are closed, the recirculation damper is open The room air circulates through the filters. Then it is returned back to the room purified.
AIR FILTRATION

Supply air cleaning is provided by the G4 and F7 filters. To meet more stringent air purity requirements the F7 filter can be replaced with an H13 Filter (purchased separately).Exhaust air is cleaned by the panel filter G4.

HEATERS

PREHEATINGFreshbox E-200 ERV WiFi, Freshbox E2-200 ERV WiFi units are equipped with an electric preheater for freeze protection of the heat exchanger.

REHEATINGFreshbox E1-200 ERV WiFi. Freshbox E2-200 ERV WiFi units feature an electric reheater to raise the supply air temperature as necessary.

FREEZE PROTECTION

The Freshbox 200 ERV WiFi features an exhaust air temperature sensor downstream of the heat exchanger which disables the supply fan to let the warm extract air warm up the heat exchanger. Then the supply fan is turned on and the unit reverts to normal operation.
Freeze protection for Freshbox E-200 ERV WiFi and Freshbox E2-200 ERV WiFi is implemented with an electric preheater.

HEAT AND ENERGY RECOVERY

The unit is equipped with a counter-flow energy recovery core with an enthalpy membrane at the core.

  • In the cold season the exhaust air heat and moisture are transferred to the supply air stream through the enthalpy membrane reducing the heat losses through ventilation.
  • Consequently, it is the intake air heat and moisture transferred to the extract air stream through the enthalpy membrane in the warm season. This allows for a considerable reduction of the supply air temperature and humidity which, in turn, reduces the air conditioning load.
CONTROL  

The unit is equipped with a control panel.The remote control is supplied as standardWi-Fi communication.

AUTOMATIC FUNCTIONS

  Freshbox 200 ERV WiFi
Freshbox E-200
ERV WiFi
Freshbox E1-200 ERV WiFi
Freshbox E2-200 ERV WiFi
Speed selection
Filter replacement indication
Alarm indication
Speed setup
Timer
Week scheduler
Reheater enabled/disabled  
Supply air temperature setup  
Control with the mobile application Android / iOS

Download
Andrioid application
Blauberg Freshbox
Download
iOS application
Blauberg Freshbox

REMOTE CONTROL

1. Turning unit on/off
2. Speed selection
3. Increasing temperature set point for the reheater (available for the models with a reheater)
4. Turning reheater on/off (available for the models with a reheater)
5. Decreasing temperature set point for the reheater (available for the models with a reheater)
6. Turning timer on/off
7. Activation/deactivation of the scheduled operation mode

CONTROL PANEL

MOUNTING EXAMPLE  

Each space requiring ventilation is equipped with one or several Freshbox 200 ERV WiFi units.

Can be upgraded with a bathroom exhaust air duct. To enable such a configuration the units can be additionally equipped with the optional ø100 mm spigot (supplied as standard).

FRESHBOX 200 ERV WIFI MOUNTING EXAMPLE IN THE OFFICE
FRESHBOX 200 ERV WIFI MOUNTING EXAMPLE IN THE APPARTMENT
Characteristics
Characteristics
Parameter Freshbox E-200 ERV WiFi
Speed I
Freshbox E-200 ERV WiFi
Speed II
Freshbox E-200 ERV WiFi
Speed III
Freshbox E-200 ERV WiFi
Speed IV
Freshbox E-200 ERV WiFi
Speed V
Measurement unit
Speed I II III IV V -
Voltage 230 230 230 230 230 V
Phase 1 1 1 1 1 ˜
Frequency 50/60 50/60 50/60 50/60 50/60 Hz
Max. current consumption with heater(s) 4.0 4.0 4.0 4.0 4.0 A
Max. power without electric heater 10 15 25 44 134 W
Reheater power consumption W
Preheater power consumption 650 650 650 650 650 W
RPM 2000 2000 2000 2000 2000 min-1
Maximum air flow 30 60 90 120 200 m³/h
Maximum air flow 8 17 25 33 56 l/s
Sound pressure level at 3 m in accordance with ISO 3741:2004 12 22 30 36 45 dBА
Transported air temperature -15...+40 -15...+40 -15...+40 -15...+40 -15...+40 °С
Extract filter G4 G4 G4 G4 G4 -
Insulation thikness 30 30 30 30 30 mm
Supply filter G4 + F7 (Option: H13) G4 + F7 (Option: H13) G4 + F7 (Option: H13) G4 + F7 (Option: H13) G4 + F7 (Option: H13) -
Heat recovery efficiency 85 81 75 68 66 %
Heat exchanger type counter-flow counter-flow counter-flow counter-flow counter-flow -
Remote control panel Sensor Wi-Fi Sensor Wi-Fi Sensor Wi-Fi Sensor Wi-Fi Sensor Wi-Fi -
Functions Wi-Fi, Filter replacement indication, Timer, Weekly schedule Wi-Fi, Filter replacement indication, Timer, Weekly schedule Wi-Fi, Filter replacement indication, Timer, Weekly schedule Wi-Fi, Filter replacement indication, Timer, Weekly schedule Wi-Fi, Filter replacement indication, Timer, Weekly schedule -
Heat exchanger material enthalpy enthalpy enthalpy enthalpy enthalpy -
Weight 55 55 55 55 55 kg
Connected air duct diameter 100 100 100 100 100 mm
Heating electric preheating electric preheating electric preheating electric preheating electric preheating -
Casing material polymer-coated steel polymer-coated steel polymer-coated steel polymer-coated steel polymer-coated steel -
SEC class A A A A A -
Capacity diagram
Capacity diagram
  • Selection method:
  • Air capacity:
  • Pressure:
Operating point
  • Air capacity: --
  • Pressure: ---
Documents archieve
Documents archieve
Select a document type
  • Catalogues
  • Technical documentation
  • Certificates
Name
Freshbox 200 ERV WiFi - data sheet (pdf 1.37Mb)
Freshbox 200 ERV WiFi - image (png 255.4Kb)
Freshbox 200 ERV WiFi - user's manual (pdf 2.57Mb)
Freshbox E-200 ERV WiFi - Energy Label (pdf 55.67Kb)
Freshbox E-200 ERV WiFi - Specification (pdf 35.6Kb)
Catalogue "Single-room ventilation for countries with hot and humid climates" (pdf 20.19Mb)
Designation key
Designation key
Model Heater   Rated air flow [m³/h] Heat exchanger type Control
Freshbox

_: no heater
Е: preheating
Е1: reheating
Е2: preheating + reheating

- 200 ERV: energy recovery WiFi: sensor control panel and Wi-Fi communication
Dimensions
Dimensions

Accessories
Accessories
Name  Description
MS Freshbox 200 chrome

Mounting kit:

  • Two ∅ 100 mm air ducts, 500 mm long
  • Ventilation outer hood made of polished steel
  • Cardboard template
MS Freshbox 200 white

Mounting kit:

  • Two ∅ 100 mm air ducts, 500 mm long
  • Ventilation outer hood, painted white
  • Cardboard template
AH Freshbox 200 chrome Ventilation outer hood made of polished steel
AH Freshbox 200 white Ventilation outer hood, painted white
FP 201x162x20 G4 Exhaust G4 cassette filter
FP 243x162x20 G4 Supply G4 cassette filter
FP 502х162х40 F7 Supply F7 cassette filter
FP 502x162x40 Н13 Supply HEPA H13 cassette filter
HR-S Humidity sensor
 CD-1

CO2 sensor with LED CO2 indication and a sensor button for operation mode selection

CD-2

CO2 Sensor