FEATURES | |||||||||||||||||||||||||||||||||||||||||||
Efficient solution for supply and exhaust ventilation of enclosed spaces.EC fans with low energy consumption.Supply air cleaning is provided by the G4 and F7 filters. Additional air purification due to recirculation. H13 filter is available as an option.Upgradeable with an exhaust duct to provide air extraction from the bathroom.Easy installation.Compact size.Controlled by Android or iOS smartphone or tablet over Wi-Fi. |
|||||||||||||||||||||||||||||||||||||||||||
DESIGN | MOTORS | ||||||||||||||||||||||||||||||||||||||||||
The casing is made of polymer coated steel plates.The front panel provides convenient access for filter maintenance and has a lock for extra security.The unit has two Ø 100 mm pipes for fresh air intake and stale air extraction outside. The third Ø 100 mm pipe (included in the scope of delivery) can be additionally fitted to the unit to connect the exhaust air duct from the bathroom.Available modifications with an integrated preheater and reheater for cold climate applications. |
The units feature efficient electronically commutated (EC) motors with an external rotor and impellers with forward curved blades. These stateofthe-art motors are the most advanced solution in energy efficiency today.EC motors are characterised with high performance and optimum control across the entire speed range. In addition to that the efficiency of electronically commutated motors reaches very impressive levels of up to 90 %. |
||||||||||||||||||||||||||||||||||||||||||
AIR DAMPERS | OPERATING PRINCIPLE | ||||||||||||||||||||||||||||||||||||||||||
The unit is equipped with supply and exhaust air dampers which activate automatically to prevent drafts while the unit is off. |
HEAT RECOVERY OPERATION MODE
|
||||||||||||||||||||||||||||||||||||||||||
AIR FILTRATION | |||||||||||||||||||||||||||||||||||||||||||
Supply air cleaning is provided by the G4 and F7 filters. To meet more stringent air purity requirements the F7 filter can be replaced with an H13 Filter (purchased separately).Exhaust air is cleaned by the panel filter G4. |
|||||||||||||||||||||||||||||||||||||||||||
HEATERS | |||||||||||||||||||||||||||||||||||||||||||
PREHEATINGFreshbox E-200 ERV WiFi, Freshbox E2-200 ERV WiFi units are equipped with an electric preheater for freeze protection of the heat exchanger. REHEATINGFreshbox E1-200 ERV WiFi. Freshbox E2-200 ERV WiFi units feature an electric reheater to raise the supply air temperature as necessary. |
|||||||||||||||||||||||||||||||||||||||||||
FREEZE PROTECTION | |||||||||||||||||||||||||||||||||||||||||||
The Freshbox 200 ERV WiFi features an exhaust air temperature sensor downstream of the heat exchanger which disables the supply fan to let the warm extract air warm up the heat exchanger. Then the supply fan is turned on and the unit reverts to normal operation. |
|||||||||||||||||||||||||||||||||||||||||||
HEAT AND ENERGY RECOVERY | |||||||||||||||||||||||||||||||||||||||||||
The unit is equipped with a counter-flow energy recovery core with an enthalpy membrane at the core.
|
|||||||||||||||||||||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||||||||||||||
MOUNTING EXAMPLE | |||||||||||||||||||||||||||||||||||||||||||
Each space requiring ventilation is equipped with one or several Freshbox 200 ERV WiFi units. |
Can be upgraded with a bathroom exhaust air duct. To enable such a configuration the units can be additionally equipped with the optional ø100 mm spigot (supplied as standard). |
||||||||||||||||||||||||||||||||||||||||||
FRESHBOX 200 ERV WIFI MOUNTING EXAMPLE IN THE OFFICE | |||||||||||||||||||||||||||||||||||||||||||
FRESHBOX 200 ERV WIFI MOUNTING EXAMPLE IN THE APPARTMENT | |||||||||||||||||||||||||||||||||||||||||||
Parameter | Freshbox E1-200 ERV WiFi Speed I |
Freshbox E1-200 ERV WiFi Speed II |
Freshbox E1-200 ERV WiFi Speed III |
Freshbox E1-200 ERV WiFi Speed IV |
Freshbox E1-200 ERV WiFi Speed V |
Measurement unit |
---|---|---|---|---|---|---|
Speed | I | II | III | IV | V | - |
Voltage | 230 | 230 | 230 | 230 | 230 | V |
Phase | 1 | 1 | 1 | 1 | 1 | ˜ |
Frequency | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | Hz |
Max. current consumption with heater(s) | 4.2 | 4.2 | 4.2 | 4.2 | 4.2 | A |
Max. power without electric heater | 10 | 15 | 25 | 44 | 134 | W |
Reheater power consumption | 700 | 700 | 700 | 700 | 700 | W |
Preheater power consumption | — | — | — | — | — | W |
RPM | 2000 | 2000 | 2000 | 2000 | 2000 | min-1 |
Maximum air flow | 30 | 60 | 90 | 120 | 200 | m³/h |
Maximum air flow | 8 | 17 | 25 | 33 | 56 | l/s |
Sound pressure level at 3 m in accordance with ISO 3741:2004 | 12 | 22 | 30 | 36 | 45 | dBА |
Transported air temperature | -15...+40 | -15...+40 | -15...+40 | -15...+40 | -15...+40 | °С |
Extract filter | G4 | G4 | G4 | G4 | G4 | - |
Insulation thikness | 30 | 30 | 30 | 30 | 30 | mm |
Supply filter | G4 + F7 (Option: H13) | G4 + F7 (Option: H13) | G4 + F7 (Option: H13) | G4 + F7 (Option: H13) | G4 + F7 (Option: H13) | - |
Heat recovery efficiency | 85 | 81 | 75 | 68 | 66 | % |
Heat exchanger type | counter-flow | counter-flow | counter-flow | counter-flow | counter-flow | - |
Remote control panel | Sensor Wi-Fi | Sensor Wi-Fi | Sensor Wi-Fi | Sensor Wi-Fi | Sensor Wi-Fi | - |
Functions | Wi-Fi, Filter replacement indication, Timer, Weekly schedule | Wi-Fi, Filter replacement indication, Timer, Weekly schedule | Wi-Fi, Filter replacement indication, Timer, Weekly schedule | Wi-Fi, Filter replacement indication, Timer, Weekly schedule | Wi-Fi, Filter replacement indication, Timer, Weekly schedule | - |
Heat exchanger material | enthalpy | enthalpy | enthalpy | enthalpy | enthalpy | - |
Weight | 55 | 55 | 55 | 55 | 55 | kg |
Connected air duct diameter | 100 | 100 | 100 | 100 | 100 | mm |
Heating | electric reheating | electric reheating | electric reheating | electric reheating | electric reheating | - |
Casing material | polymer-coated steel | polymer-coated steel | polymer-coated steel | polymer-coated steel | polymer-coated steel | - |
SEC class | A | A | A | A | A | - |
- Selection method:
- Air capacity:
- Pressure:
- Air capacity: --
- Pressure: ---
Model | Heater | Rated air flow [m³/h] | Heat exchanger type | Control | |
Freshbox |
_: no heater |
- | 200 | ERV: energy recovery | WiFi: sensor control panel and Wi-Fi communication |
Name | Description | |
MS Freshbox 200 chrome |
Mounting kit:
|
|
MS Freshbox 200 white |
Mounting kit:
|
|
AH Freshbox 200 chrome | Ventilation outer hood made of polished steel | |
AH Freshbox 200 white | Ventilation outer hood, painted white | |
FP 201x162x20 G4 | Exhaust G4 cassette filter | |
FP 243x162x20 G4 | Supply G4 cassette filter | |
FP 502х162х40 F7 | Supply F7 cassette filter | |
FP 502x162x40 Н13 | Supply HEPA H13 cassette filter | |
HR-S | Humidity sensor | |
CD-1 |
CO2 sensor with LED CO2 indication and a sensor button for operation mode selection |
|
CD-2 |
CO2 Sensor |