Blauberg inWave 150/160


Sound-insulated inline mixed-flow fan. Maximum air flow up to 540 m³/h.
EAN codeEAN4058448087479
  • Description
  • Characteristics
  • Capacity diagram
  • Downloads
  • Designation key
  • Accessories
  • Dimensions
  • Additional characteristics
Description
Description
USE

Supply and extract ventilation systems installed in various premises with high requirements to the noise level. For ventilation air ducts requiring high pressure, powerful air flow and low noise level.

 
DESIGN

The casing is made of high-quality durable plastic, internally filled with 50 mm mineral wool thermal- and sound-insulating layer. Special inner perforation of the casing and sound-insulating material are designed for wide-frequency sound absorbing. Mixed-flow impeller made of high-quality plastic. The diffusor, the specially profiled impeller and directing vanes provide high performance and powerful pressure combined with low noise operation. External airtight terminal block on the fan casing for power supply. Mounting brackets on the fan casing for mounting to the floor, to the wall or ceiling.

  MOTOR

Single-phase three-speed high-efficient motor with low energy demand on ball bearings. Overheating protection due to built-in thermal switches.

SPEED CONTROL

Speed selection with a built-in speed switch (US option) or an external multi-speed controller (specially ordered accessory). Smooth speed control is possible either with an integrated speed controller (FR1 option), an external thyristor or transformer speed controller (specially ordered accessory) when connected to the maximum speed terminal.

MOUNTING

Due to its compact design the fan is the ideal solution for mounting in limited spaces. The fan is suitable for mounting in any section of the ventilation system from intake to the end of the ductwork according to installation manual. Wall or ceiling mounting with a special bracket on the fan casing.

MODIFICATIONS AND OPTIONS

T: turn-off delay timer adjustable from 2 to 30 minutes. US: three-position speed switch. FR1: smooth speed controller adjustable from 0 to 100 % and power cable with mains plug.

G1: speed controller, temperature controller with external temperature sensor (cable length 4 m), power cable with mains plug. The G1 modification enables automatic speed control depending on indoor temperature. The optimal ventilation solution for premises requiring permanent temperature control as greenhouses, orangeries, etc. W: power cable with plug.

   
Characteristics
Characteristics
Parameter inWave 150/160
min
inWave 150/160
med
inWave 150/160
max
Measurement unit
Speed min med max -
Spigot 150/160 150/160 150/160 mm
Voltage 230 230 230 V
Phase 1 1 1 ˜
Frequency 50 50 50 Hz
Current 0.20 0.21 0.24 A
Power 25 46 51 W
RPM 1982 2374 2738 min-1
Maximum air flow 67 89 150 l/s
Maximum air flow 242 320 540 m³/h
Sound pressure level at 3 m 20 26 33 dBА
Max. operating temperature –25…+55 –25…+55 –25…+55 °С
Motor IP rating IP20 IP20 IP20 -
Ingress protection rating IPX4 IPX4 IPX4 -
EC motor no no no -
Casing material plastic plastic plastic -
Outdoor mounting no no no -
Sound-insulated casing yes yes yes -
Air duct for round air ducts for round air ducts for round air ducts -
Design mixed-flow mixed-flow mixed-flow -
Type Exhaust, Supply, Supply and exhaust Exhaust, Supply, Supply and exhaust Exhaust, Supply, Supply and exhaust -
Weight 5.0 5.0 5.0 kg
Mounting Inline Inline Inline -
ErP 2018 2018 2018 -
Capacity diagram
Capacity diagram
  • Selection method:
  • Air capacity:
  • Pressure:
Operating point
  • Air capacity: --
  • Pressure: ---
Documents archieve
Documents archieve
Select a document type
  • Catalogues
  • Technical documentation
  • Certificates
Name
inWave - image (png 277.76Kb)
inWave (EC) 150/160 - user's manual (pdf 3.42Mb)
inWave 150/160 - data sheet (pdf 500.19Kb)
Designation key
Designation key
Series Duct diameter [mm] Options
inWave 150/160 T: turn-off delay timer adjustable from 2 to 30 minutes
US: three-position speed switch
FR1: smooth speed controller adjustable from 0 to 100 % and power cable with mains plug
G1: speed controller, temperature controller with external temperature sensor, power cable with mains plug
W1: power cable with mains plug
Accessories
Accessories
Silencers Filter boxes Electric heaters Water heaters Backdraft air dampers Air dampers Clamps Speed switches Speed controllers
SD KFBK KFBT EKH WKH VRV VK / VKA K CDP-3/5 CDT1 E CDT E1.8 CDTE E... TP
Dimensions
Dimensions

Model Overall dimensions [mm]
∅ D H L W
inWave 150/160 (spigot 150 mm) 149 273 606 253
inWave 150/160 (spigot 160 mm) 159 273 606 253
Additional characteristics
Additional characteristics
Sound power level, A-weighted Total Octave frequency bands [Hz] LpA 3 m LpA 1 m
63 125 250 500 1000 2000 4000 8000
LwA to inlet [dBA] 61 37 56 59 48 41 38 41 34 41 51
LwA to outlet [dBA] 60 32 52 58 47 37 36 41 35 39 49
LwA to environment [dBA] 53 33 50 49 40 35 30 30 24 33 43