USE
Supply and extract ventilation systems installed in various premises with high requirements to the noise level. For ventilation air ducts requiring high pressure, powerful air flow and low noise level. |
||
DESIGN
The casing is made of high-quality durable plastic, internally filled with 50 mm mineral wool thermal- and sound-insulating layer. Special inner perforation of the casing and sound-insulating material are designed for wide-frequency sound absorbing. Mixed-flow impeller made of high-quality plastic. The diffusor, the specially profiled impeller and directing vanes provide high performance and powerful pressure combined with low noise operation. External airtight terminal block on the fan casing for power supply. Mounting brackets on the fan casing for mounting to the floor, to the wall or ceiling. |
MOTOR
Single-phase three-speed high-efficient motor with low energy demand on ball bearings. Overheating protection due to built-in thermal switches. SPEED CONTROLSpeed selection with a built-in speed switch (US option) or an external multi-speed controller (specially ordered accessory). Smooth speed control is possible either with an integrated speed controller (FR1 option), an external thyristor or transformer speed controller (specially ordered accessory) when connected to the maximum speed terminal. MOUNTINGDue to its compact design the fan is the ideal solution for mounting in limited spaces. The fan is suitable for mounting in any section of the ventilation system from intake to the end of the ductwork according to installation manual. Wall or ceiling mounting with a special bracket on the fan casing. |
|
MODIFICATIONS AND OPTIONS
T: turn-off delay timer adjustable from 2 to 30 minutes. US: three-position speed switch. FR1: smooth speed controller adjustable from 0 to 100 % and power cable with mains plug. G1: speed controller, temperature controller with external temperature sensor (cable length 4 m), power cable with mains plug. The G1 modification enables automatic speed control depending on indoor temperature. The optimal ventilation solution for premises requiring permanent temperature control as greenhouses, orangeries, etc. W: power cable with plug. |
Parameter | inWave 150/160 min |
inWave 150/160 med |
inWave 150/160 max |
Measurement unit |
---|---|---|---|---|
Speed | min | med | max | - |
Spigot | 150/160 | 150/160 | 150/160 | mm |
Voltage | 230 | 230 | 230 | V |
Phase | 1 | 1 | 1 | ˜ |
Frequency | 50 | 50 | 50 | Hz |
Current | 0.20 | 0.21 | 0.24 | A |
Power | 25 | 46 | 51 | W |
RPM | 1982 | 2374 | 2738 | min-1 |
Maximum air flow | 67 | 89 | 150 | l/s |
Maximum air flow | 242 | 320 | 540 | m³/h |
Sound pressure level at 3 m | 20 | 26 | 33 | dBА |
Max. operating temperature | –25…+55 | –25…+55 | –25…+55 | °С |
Motor IP rating | IP20 | IP20 | IP20 | - |
Ingress protection rating | IPX4 | IPX4 | IPX4 | - |
EC motor | no | no | no | - |
Casing material | plastic | plastic | plastic | - |
Outdoor mounting | no | no | no | - |
Sound-insulated casing | yes | yes | yes | - |
Air duct | for round air ducts | for round air ducts | for round air ducts | - |
Design | mixed-flow | mixed-flow | mixed-flow | - |
Type | Exhaust, Supply, Supply and exhaust | Exhaust, Supply, Supply and exhaust | Exhaust, Supply, Supply and exhaust | - |
Weight | 5.0 | 5.0 | 5.0 | kg |
Mounting | Inline | Inline | Inline | - |
ErP | 2018 | 2018 | 2018 | - |
- Selection method:
- Air capacity:
- Pressure:
- Air capacity: --
- Pressure: ---
Series | Duct diameter [mm] | Options |
inWave | 150/160 | T: turn-off delay timer adjustable from 2 to 30 minutes US: three-position speed switch FR1: smooth speed controller adjustable from 0 to 100 % and power cable with mains plug G1: speed controller, temperature controller with external temperature sensor, power cable with mains plug W1: power cable with mains plug |
Model | Overall dimensions [mm] | |||
∅ D | H | L | W | |
inWave 150/160 (spigot 150 mm) | 149 | 273 | 606 | 253 |
inWave 150/160 (spigot 160 mm) | 159 | 273 | 606 | 253 |
Sound power level, A-weighted | Total | Octave frequency bands [Hz] | LpA 3 m | LpA 1 m | |||||||
63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | ||||
LwA to inlet [dBA] | 61 | 37 | 56 | 59 | 48 | 41 | 38 | 41 | 34 | 41 | 51 |
LwA to outlet [dBA] | 60 | 32 | 52 | 58 | 47 | 37 | 36 | 41 | 35 | 39 | 49 |
LwA to environment [dBA] | 53 | 33 | 50 | 49 | 40 | 35 | 30 | 30 | 24 | 33 | 43 |