FEATURES
Air handling units for efficient supply and exhaust ventilation in flats, houses, cottages and other buildings. The heat recovery technology is used to minimize ventilation heat losses. Control of air exchange for creating comfortable indoor microclimate. Compatible with round Ø 125 mm air ducts. FANSThe unit is equipped with high-efficient external rotor EC motors and centrifugal impellers with forward curved blades. EC motors have the best power consumption to air flow ratio and meet the latest demands concerning energy saving and high-efficient ventilation. EC motors are featured with high performance, low noise level and totally controllable speed range. The impellers are dynamically balanced. |
DESIGN
The casing of KOMFORT Ultra EC L2 300 … white is made of double-skinned white painted metal panels, internally filled with 20 mm mineral wool layer for heat- and sound-insulation. The spigots are located at the sides of the unit and are equipped with rubber seals for airtight connection to the air ducts. The hinged panel of the casing ensures easy access to the unit internals for service works including cleaning, filter replacement, etc. |
|
HEAT RECOVERY
The KOMFORT Ultra EC L2 300-H … white unit is equipped with a plate cross-flow polystyrene heat exchanger for heat recovery. The unit condensate is collected and drained to the drain pan under the heat exchanger. The KOMFORT Ultra EC L2 300-E … white unit is equipped with an enthalpy plate cross-flow heat exchanger for energy (heat and humidity) recovery. Due to humidity recovery condensate is not generated in the enthalpy heat exchanger. The air flows are completely separated in the heat exchanger. Thus smells and contaminants are not transferred from the extract air to the supply air. Heat recovery is based on heat and/or humidity transfer through the heat exchanger plates. In the cold season supply air is heated in the heat exchanger by transferring the heat energy of warm and humid extract air to the cold fresh air. Heat recovery minimizes ventilation heat losses and heating costs respectively. In the warm season the heat exchanger performs reverse and intake air is cooled in the heat exchanger by the cool extract air. That reduces operation load on air conditioners and saves electricity. When the indoor and outdoor temperature difference is insignificant, heat recovery is not reasonable. In this case the heat exchanger can be temporary replaced with a summer block for the warm season (available as a specially ordered accessory). FREEZE PROTECTIONThe integrated automatic freeze protection is used to prevent freezing of the heat exchanger in the cold season. The supply fan turns off according to the temperature sensor to get the heat exchanger warmed up with extract air. After that the supply fan turns on and the unit continues to run in the standard mode. AIR FILTRATIONTwo built-in G4 and F8 filters provide efficient supply air filtration. The G4 filter is used for extract air filtration. |
CONTROL AND AUTOMATION
The KOMFORT Ultra EC L2 300-H(E) S2 white unit is equipped with the CDT E/0-10 speed controller that is included in the delivery. The KOMFORT Ultra EC L2 300-H(E) S14 white units have an integrated control system with a wall-mounted control panel S14 with a LED indication. The S14 control panel functions:
The KOMFORT Ultra EC L2 300-H(E) S14 white unit is equipped with a USB connector (Type B) and can be connected to a PC for configuring the advanced settings in a special software:
The units can be fixed to the wall or mounted on the floor using the mounting brackets. The KOMFORT Ultra EC L2 300-E … white unit is also suitable for ceiling mounting. The KOMFORT Ultra EC L2 300-H … white unit mounting position must provide condensate collection and drainage. While mounting provide free access to the service panel for filter replacement and servicing. Due to universal casing design both left and right mounting is possible. It requires swapping the service and the back panel. |
Parameter | KOMFORT Ultra EC L2 300-H S14 white | Measurement unit |
---|---|---|
Voltage | 230 | V |
Phase | 1 | ˜ |
Frequency | 50/60 | Hz |
Power | 165 | W |
Current | 1.3 | A |
Maximum air flow | 83 | l/s |
Maximum air flow | 300 | m³/h |
Sound pressure level at 3 m | 33 | dBА |
Insulation | 20 mm mineral wool | mm |
Transported air temperature | -25...+40 | °С |
Extract filter | G4 | - |
Supply filter | F8, G4 | - |
Heat recovery efficiency | 55...79 | % |
EC motor | yes | - |
Heat exchanger type | cross-flow | - |
Heat exchanger material | polystyrene | - |
Weight | 32 | kg |
Outdoor mounting | no | - |
Sound-insulated casing | yes | - |
Air duct | for round air ducts | - |
Connection diameter | 125 | mm |
Type | Supply and exhaust | - |
SEC class | A | - |
Mounting | wall mounting, floor mounting | - |
ErP | 2016, 2018 | - |
- Selection method:
- Air capacity:
- Pressure:
- Air capacity: --
- Pressure: ---
Series | Unit type | Motor type | Spigot modification | Insulation | Rated air flow [m³/h] | Heat exchanger type | Control | Casing | |
KOMFORT | Ultra: compact unit | ЕС: electronically commutated motor | L: horizontal spigot orientation | 2: insulation 20 mm | 300 | – | Н: heat recovery Е: energy recovery |
S2: CDT E/0-10 speed controller S14: sensor control panel with LED indication |
white: painted steel |
KOMFORT Ultra EC L2 300-H S14 white | ||
G4 panel filter | FP 240x184x40 G4 | |
F8 panel filter | FP 240x184x40 F8 | |
Humidity sensor | FS2 | |
CO2 sensor with indication | CD-1 | |
CO2 sensor | CD-2 | |
Humidity sensor | HR-S | |
Silencer | SD 125 | |
Backdraft air damper | VRV 125 | |
Air damper | VKA 125 | |
Electric actuator | TF230 | |
Summer block | SB C4 200/240 |
|
Sound power level, A-weighted | Octave frequency band [Hz] | LpA 3 m | LpA 1 m | ||||||||
Total | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||
LwA to supply inlet [dBA] | 56 | 48 | 43 | 53 | 44 | 44 | 40 | 26 | 24 | ||
LwA to supply outlet [dBA] | 71 | 53 | 53 | 68 | 65 | 60 | 59 | 52 | 51 | ||
LwA to exhaust inlet [dBA] | 57 | 43 | 51 | 52 | 52 | 45 | 37 | 26 | 21 | ||
LwA to exhaust outlet [dBA] | 72 | 53 | 60 | 66 | 67 | 61 | 62 | 55 | 48 | ||
LwA to environment [dBA] | 53 | 33 | 44 | 47 | 50 | 44 | 38 | 29 | 24 | 33 | 43 |
* Data provided for point 1 of the air flow diagram
Model | Dimensions [mm] | |||||
D | B | H | H1 | L | L1 | |
KOMFORT Ultra EC L2 300-H S14 white | 125 | 300 | 443 | 63 | 713 | 810 |