Login
Not registered yet? Take advantages of registration:
Products saving in a binding to the projects
Online consultation from experts
Signup

Privacy policy

Blauberg EVH (round)

  • Description
  • Modifications
  • Downloads
  • Designation key
  • Compatibility chart
  • Heater capacity selection diagram
Description
Description
FEATURES

Heat exchanger freeze protection by means of preheating of the intake air. Maintains the duct air temperature at a point that prevents the heat exchanger freezing. Compatible with Ø 125 up to 250 mm air ducts.

CONTROL

Equipped with a power cable. The signal cable for connection to the controller of the air handling unit. Equipped with a triac power regulator.Regulation is carried out via switching-on and switching-off the full load. Load commutation is carried out by the semiconductor device (triac). The switching unit has no wearing mechanical elements. Equipped with overheat thermostats:

  • main protection with automatic restart at +50 °С;
  • emergency protection with manual restart at +90 °С.
  DESIGN

The casing is internally filled with 20 mm layer of non-flammable mineral wool. The casing and the junction box are made of galvanized steel. Heating elements are made of stainless steel. Airtight connection to air ducts due to rubber seals.

MOUNTING

Fixation to round air ducts by means of clamp (included in the delivery). In case of horizontal mounting position the control box cover must be directed upwards only. Permitted deviation up to 90°. The control box cover may not be positioned downwards!

Modifications
Modification name
EVH 125-0.6-1
EVH 125-0.8-1
EVH 125-1.2-1
EVH 150-0.8-1
EVH 150-1.2-1
EVH 150-1.7-1
EVH 150-2.0-1
EVH 160-0.8-1
EVH 160-1.2-1
EVH 160-1.7-1
EVH 160-2.0-1
EVH 200-1.2-1
EVH 200-1.7-1
EVH 200-2.0-1
EVH 250-1.2-1
EVH 250-2.0-1
EVH 250-3.0-1
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
Documents archieve
Documents archieve
Select a document type
  • Catalogues
  • Technical documentation
  • Certificates
Name
EVH (round) - data sheet (pdf 436.99Kb)
EVH (round) - image (png 583.53Kb)
EVH (round) - user's manual (pdf 1.31Mb)
Designation key
Designation key
Series Connected air duct diameter [mm]   Heater power [kW]   Number of phases
EVH 125; 150; 160; 200; 250 0.6; 0.8; 1.2; 1.7; 2.0; 3.0 1: single-phase
Compatibility chart
Compatibility chart
Heater model Unit model
EVH 125 KOMFORT with spigot Ø 125 mm and S21 control panel
EVH 150 KOMFORT with spigot Ø 150 mm and S21 control panel
EVH 160 KOMFORT with spigot Ø 160 mm and S21 control panel
EVH 200 KOMFORT with spigot Ø 200 mm and S21 control panel
EVH 250 KOMFORT with spigot Ø 250 mm and S21 control panel
Heater capacity selection diagram
Heater capacity selection diagram
EVH heater parameters calculation example: It is necessary to select EVH freeze protection heater for the KOMFORT EC SB 350 S21 unit. Design outdoor air temperature in cold season is -15 °C. Design capacity is 220 m³/h.Identify the interception point of the air flow line (1) with the outdoor temperature line (2). In this case the heater with the capacity of 1200 W will assure efficient freeze protection of the heat exchanger. Select the EVH 160-1.2-1 heater with the diameter corresponding to the diameter of the spigot of the KOMFORT EC SB 350 S21 unit.