Login
Not registered yet? Take advantages of registration:
Products saving in a binding to the projects
Online consultation from experts
Signup

Privacy policy

Blauberg ALB-30


Unit for air cooling and heating. Maximum air flow up to 3000 m³/h.
EAN codeEAN4058448063718
  • Description
  • Characteristics
  • Downloads
  • Dimensions
  • Additional characteristics
Description
Description
USE

Air heating or cooling with water heater and its smooth distribution in a room with a fan and louvre shutters. Arranging of energy efficient air heating or cooling in various premises including medium and large-scale buildings. Local heating or cooling of job sites or separate areas.

DESIGN

The unit consists of a high-performance axial fan and a high-efficient copper-aluminium water heater. Steel polymer-coated casing equipped with louvre shutters for uniform air distribution. The water coils are equipped with internally threaded pipes on the casing side for connection to the heat medium. Fixing brackets are designed for wall or ceiling mounting.

MOTOR

Asynchronous external rotor motor and axial impeller. Single-phase motor. Equipped with ball bearings for longer service life. Integrated thermal protection with automatic restart.

SPEED CONTROL

Smooth speed control with an external thyristor controller or step speed control with an external auto transformer (both available upon separate order). Fan speed control provides regulation of the air flow and respectively the thermal transmission for heating or cooling. The SGWH control unit is used for controlling the operation modes of the air heating (cooling) unit (available upon separate order).

MOUNTING

The units may be installed vertically on walls or columns or horizontally on ceiling or beams.

Characteristics
Characteristics
Parameter ALB-30 Measurement unit
Voltage 220-240 V
Frequency 50 Hz
Fan current 0.85 A
Power 191 W
RPM 1440 min-1
Maximum air flow 833 l/s
Maximum air flow 3000 m³/h
Sound pressure level at 3 m 55 dBА
Maximum heat medium temperature +100 °С
Motor IP rating IP44 -
Insulation class B -
Ingress protection rating IP44 -
EC motor no -
Weight 40 kg
Casing material polymer-coated steel -
Outdoor mounting no -
Sound-insulated casing no -
Air duct for round air ducts -
Design axial -
Type Supply -
Mounting ceiling mounting, wall mounting -
Documents archieve
Documents archieve
Select a document type
  • Catalogues
  • Technical documentation
  • Certificates
Name
ALB - data sheet (pdf 597.06Kb)
ALB - image (png 674.61Kb)
ALB - user's manual (pdf 1.97Mb)
Dimensions
Dimensions

Model Overall dimensions [mm] Number of tube raw
B B1 H H1 L L2 K
ALB-30 680 785 655 518 360 286 G 3/4” 2
Additional characteristics
Additional characteristics

TECHNICAL DATA FOR HEATING MODE

Air flow [m³/h (l/s)] Water inlet temperature [°C] Supply air temperature [°C] ALB-30
Power [kW] Outlet temperature [°C] Water flow rate [l/s] Water pressure loss [kPa]
3000 (833) 90/70 -15 48.4 27.2 0.58 7.4
-10 45.4 30.3 0.56 6.6
-5 42.4 33.4 0.53 5.9
0 39.5 36.4 0.47 5.2
5 36.7 39.4 0.44 4.5
10 33.8 42.1 0.42 3.9
15 31 44.9 0.39 3.3
80/60 -15 42 22 0.53 6.0
-10 39 25.2 0.47 5.3
-5 36.7 28.2 0.44 4.6
0 33.8 31.1 0.42 3.9
5 30.9 34.0 0.39 3.4
10 28.1 36.7 0.33 2.8
15 25.3 40 0.31 2.3
70/50 -15 36.6 17 0.44 4.7
-10 33.7 20 0.42 4.0
-5 30 22.9 0.39 3.4
0 28 25.7 0.33 2.9
5 25 28.5 0.31 2.4
10 22 31.1 0.28 1.9
15 19.4 33.7 0.25 1.5
60/40 -15 31 11.7 0.36 3.5
-10 27.6 14.6 0.33 2.9
-5 24 17.4 0.31 2.4
0 21 20 0.28 1.9
5 19 22.7 0.22 1.5
10 16 25.2 0.19 1.1
15 13 27.5 0.17 0.7

 

TECHNICAL DATA FOR COOLING MODE

Air flow [m³/h (l/s)] Water inlet temperature [°C] Supply air temperature [°C] ALB-30
Power [kW] Outlet temperature [°C] Water flow rate [l/s] Water pressure loss [kPa]
3000 (833) 7/12 35 11.4 27 0.56 11.2
30 7.3 22.9 0.36 5.0
25 3.9 21.1 0.19 1.6
20 2.4 17.7 0.11 0.7