Blauberg Iso-Mix 200


Sound-insulated inline mixed-flow fan.
Maximum air flow up to 1035 m³/h.
EAN codeEAN4058448016684
  • Description
  • Characteristics
  • Capacity diagram
  • Downloads
  • Designation key
  • Dimensions
  • Additional characteristics
  • Accessories
Description
Description
USE

Supply and extract ventilation systems installed in various premises with high requirements to the noise level. For ventilation air ducts requiring high pressure, powerful air flow and low noise level. Compatible with Ø 100 up to Ø 315 mm air ducts.

DESIGN

The casing is made of polymer-coated steel, internally filled with 50 mm mineral wool thermal- and sound-insulating layer. Special inner perforation of the casing and sound-insulating material are designed for wide-frequency sound absorbing. Mixed-flow impeller made of high-quality plastic. The diffusor, the specially profiled impeller and directing vanes provide high performance and powerful pressure combined with low noise operation. External airtight terminal block on the fan casing for power supply. Mounting brackets on the fan casing for mounting to the floor, to the wall or ceiling.

MOTOR

Double-speed (three-speed for Iso-Mix 200) single-phase high-efficient motor with low energy demand on ball bearings. Overheating protection due to built-in thermal switches. Motor ingress protection rating IPX4.

SPEED CONTROL

Speed selection with a built-in speed switch (US option) or an external multi-speed controller (specially ordered accessory). Smooth speed control is possible either with an integrated speed controller (FR1 option), an external thyristor or transformer speed controller (specially ordered accessory) when connected to the maximum speed terminal.

MOUNTING

Due to its compact design the fan is the ideal solution for mounting in limited spaces. The fan is suitable for mounting in any section of the ventilation system from intake to the end of the ductwork. Wall or ceiling mounting with a special mounting plate on the fan casing.

  MODIFICATIONS AND OPTIONS

T: turn-off delay timer adjustable from 2 to 30 minutes. US: three-position speed switch. FR1: smooth speed controller adjustable from 0 to 100 % and power cable with mains plug.

G1: speed controller, temperature controller with external temperature sensor (cable length 4 m), power cable with mains plug.

GT1: speed controller, temperature controller with external temperature sensor (cable length 4 m), 5 min timer switch and power cable with mains plug. GI1: speed controller, temperature controller with integrated temperature sensor and power cable with mains plug. GTI1: speed controller, temperature controller with integrated temperature sensor, 5 min timer switch and power cable with mains plug. The G1 and GI1 modifications enable automatic speed control depending on indoor temperature. The optimal ventilation solution for premises requiring permanent temperature control as greenhouses, orangeries, etc. W1: power cable with mains plug.

Characteristics
Characteristics
Parameter Iso-Mix 200 min Iso-Mix 200 max Iso-Mix 200 mid Measurement unit
Speed min max med -
Voltage 230 230 230 V
Phase 1 1 1 ˜
Frequency 50/60 50/60 50/60 Hz
Power 82 110 100 W
Current 0.37 0.49 0.44 A
RPM 2376 2445 2382 min-1
Maximum air flow 203 288 267 l/s
Maximum air flow 731 1035 961 m³/h
Sound pressure level at 3 m 30 36 34 dBА
Max. operating temperature +60 +60 +60 °С
Motor IP rating IP44 IP44 IP44 -
Ingress protection rating IPX4 IPX4 IPX4 -
EC motor no no no -
Casing material polymer-coated steel polymer-coated steel polymer-coated steel -
Outdoor mounting no no no -
Sound-insulated casing yes yes yes -
Air duct for round air ducts for round air ducts for round air ducts -
Design mixed-flow mixed-flow mixed-flow -
Type Exhaust, Supply Exhaust, Supply Exhaust, Supply -
SEC class C C C -
Weight 8 8 8 kg
Mounting Inline Inline Inline -
ErP 2018 2018 2018 -
Capacity diagram
Capacity diagram
  • Selection method:
  • Air capacity:
  • Pressure:
Operating point
  • Air capacity: --
  • Pressure: ---
Documents archieve
Documents archieve
Select a document type
  • Catalogues
  • Technical documentation
  • Certificates
Name
Iso-Mix - data sheet (pdf 1.08Mb)
Iso-Mix - image (png 489.12Kb)
Iso-Mix - certificate GS (pdf 220.97Kb)
Iso-Mix - certificate LVD (pdf 132.52Kb)
Iso-Mix (100-315) - user's manual (pdf 3.81Mb)
Iso-Mix 200 - energy label (pdf 55.64Kb)
Iso-Mix 200 - specification (pdf 33.53Kb)
Iso-Mix 200 - user's manual (pdf 2.74Mb)
Designation key
Designation key
Series Duct diameter [mm] Options
Iso-Mix 100; 125; 150; 160; 200; 250; 315 T: turn-off delay timer adjustable from 2 to 30 minutes
US: three-position speed switch
FR1: smooth speed controller adjustable from 0 to 100 % and power cable with mains plug
G1: speed controller, temperature controller with external temperature sensor, power cable with mains plug
GT1: speed controller, temperature controller with external temperature sensor, 5 min timer switch and power cable with mains plug
GI1: speed controller, temperature controller with integrated temperature sensor and power cable mains plug
GTI1: speed controller, temperature controller with integrated temperature sensor, 5 min timer switch and power cable with mains plug
W1: power cable with mains plug
Dimensions
Dimensions

Model Overall dimensions [mm]
∅ D B B1 L H
Iso-Mix 200 198 293 386 550 295
Additional characteristics
Additional characteristics

To comply with ErP 2018 it is necessary to use a speed controller and local demand control typology (connect the sensor).

Sound power level, A-weighted Total Octave frequency bands [Hz] LpA 3 m LpA 1 m
63 125 250 500 1000 2000 4000 8000
Min speed                      
LwA to inlet [dBA] 63 34 53 60 57 56 41 31 17 43 53
LwA to outlet [dBA] 62 43 46 53 56 58 53 46 36 41 51
LwA to environment [dBA] 52 40 46 46 44 41 37 35 30 31 41
Max speed                      
LwA to inlet [dBA] 69 38 59 66 63 62 45 34 18 49 59
LwA to outlet [dBA] 67 39 44 48 66 58 48 48 32 47 57
LwA to environment [dBA] 57 44 52 52 49 45 41 39 34 36 46
Accessories
Accessories
Silencers
Filter boxes
Electric heaters Water heaters Backdraft air dampers
Air dampers
Clamps Temperature controllers
Speed controllers
Timers/Sensors
                    
SD KFBK / KFBT EKH WKH

VRV