Blauberg WKH 150-2


Duct water heater for round ducts.
EAN codeEAN4058448032660
  • Description
  • Characteristics
  • Downloads
  • Designation key
  • Dimensions
  • Air pressure loss
  • Calculation diagram
Description
Description
FEATURES

For warming up of supply air in ventilation systems installed in various premises. Suitable for installation in supply or air handling units to warm up the supply air flow. For indoor use only if water serves as a heat carrier. For outdoor use antifreezing mixture (ethylene glycol solution). Compatible with Ø 100 to 315 mm round air ducts.

DESIGN

Galvanized steel casing. Copper pipe manifold. Heat exchange surface made of aluminium plates. Airtight connection with air ducts due to rubber seals. Equipped with a nipple for the system deaeration. Outlet header is equipped with a spigot for installation of an immersion temperature sensor or freezing protection mechanism. Available in two- or four-row coil modifications. Suitable for operation at maximum operating pressure 1.6 MPa (16 bar) and maximum operating temperature +100 °C.

  MOUNTING

Fixing to round ducts with clamps. Any mounting position that ensures the heater deaeration. Install a filter upstream to the heater to protect heating elements against dirt ingress. Install the heater in front or behind the fan. In case of mounting behind the fan ensure a distance of not less than two connecting diameters for air flow stabilization and keep the maximum permissible air temperature inside the fan. Connect the heater on counter-flow basis, otherwise its capacity drops by 5–15 %. All the nomographic charts are rated for counter-flow connection. For correct and safe heater operation an automatic control and protection system is recommended, including the following functions:

  • regulation of the heating capacity and temperature of the air heated up;
  • filter clogging control by a differential air pressure sensor;
  • ventilation system start-up with pre-heated heater;
  • use of air dampers fitted with a spring return actuator;
  • fan turns off in case of freezing danger for the heater.

Characteristics
Characteristics
Parameter WKH 150-2 Measurement unit
Number of water coil rows 2 -
Weight 7.5 kg
Casing material galvanized steel -
Air duct for round air ducts -
Connection diameter 150 mm
Documents archieve
Documents archieve
Select a document type
  • Catalogues
  • Technical documentation
  • Certificates
Name
WKH (round) - data sheet (pdf 707.99Kb)
WKH (round) - user's manual (pdf 984.3Kb)
WKH (round) - image (png 878.01Kb)
Designation key
Designation key
Series Connected air duct diameter [mm]   Number of water (glycol) coil rows
WKH 100; 125; 150; 160; 200; 250; 315 2; 4
Dimensions
Dimensions

Model Overall dimensions [mm]
D B H H2 L L1 L2 L3 K
WKH 150-2 150 400 290 200 300 82 43 220 G 3/4”
Air pressure loss
Air pressure loss

Calculation diagram
Calculation diagram

How to use water heater diagrams. System Parameters: Air flow = 700 m³/h. Outside air temperature = -10 °C. Water temperature (in/out) = +90/+70 °C. The air flow is 700 m³/h and the air speed in the heater is 4.4 m/s .

   
To calculate the maximum air temperature find the intersection point of the air flow line with the rated outer temperature shown in blue line (e.g., -10 °C) and draw the line to the left until it crosses the water in/out temperature curve (e.g., +90/+70). From this point draw a vertical line to the supply air temperature downstream of the heater (+21 °C) . To calculate the heater power find the intersection point of the air flow with the rated winter temperature shown in red line (e.g., -10 °C) and draw the line to the right until it crosses the water in/out temperature curve (e.g., +90/+70). From this point draw a vertical line to the heater power axis (8.6 kW) .   To calculate the required water flow in the heater prolong this line downwards to the water flow axis (0.11 l/s). To calculate the water pressure drop in the heater find the intersection point of the line with the pressure loss curve and prolong the line to the right on the water pressure drop axis (8.2 kPa).