Blauberg Blaubox EC MW 2000 S31
- Description
- Characteristics
- Downloads
- Designation key
- Accessories
- Overall dimensions
- Additional diagrams
FEATURES
Ventilation units for efficient supply ventilation in various premises.Controllable air supply, heating and filtration.BMS connection via ModBUS RTU. |
||||||||||||||||||||||||||||||||||||||||||||||||||
DESIGN
Steel casing covered with aluzinc coating internally filled with 30 mm heat- and sound-insulating layer made of mineral wool.Mounting brackets with anti-vibration rubber. Service panel ensures easy access to the internals.Blaubox EC MW 700 is compatible with round ducts. |
|
|||||||||||||||||||||||||||||||||||||||||||||||||
Blaubox EC MW 700 Blaubox EC MW 1000 … 4000 |
||||||||||||||||||||||||||||||||||||||||||||||||||
FANS
Efficient external rotor EC-motors and centrifugal impellers with backward curved blades.EC-motors are featured with high performance, low noise level and totally controllable speed range.Dynamically balanced impeller. AIR FILTRATIONPanel Coarse 90% (G4) filter for supply air purification.Panel ePM10 70% (F7) filter is available as an option. AIR HEATERThe unit is equipped with a water heater. Integrated frost protection. MOUNTINGThe unit is suitable for indoor mounting on the floor, ceiling mounting or wall mounting with fixing brackets in any mounting position, except for the vertical one with air flow downwards. The correct mounted unit must provide free access to the service panel. CONTROL AND AUTOMATIONThe units are equipped with an S31 integrated automation control system. Remote control panels are not included in the delivery set and ordered separately. |
AUTOMATION FUNCTIONS
|
Parameter | Blaubox EC MW 2000 S31 | Measurement unit |
---|---|---|
Voltage | 230 | V |
Phase | 1 | ˜ |
Frequency | 50 | Hz |
Max. unit power | 387 | W |
Max. unit current | 1.7 | A |
Maximum air flow | 2150 | m³/h |
Number of water coil rows | 4 | - |
Sound pressure level at 3 m | 53 | dBА |
Water coil connection diameter | 1 | in |
Insulation | 30 mm mineral wool | mm |
Max. water temperature | 150 | °С |
Transported air temperature | -30…+40 | °С |
Filter | Coarce 90% / G4 (option: ePM1 70% / F7) | - |
EC motor | yes | - |
Weight | 45 | kg |
Connected air duct diameter | 500 x 300 | mm |
Casing material | aluzinc | - |
Outdoor mounting | no | - |
Air duct | for rectangular air ducts | - |
Design | centrifugal | - |
Type | Supply | - |
Mounting | ceiling mounting, wall mounting, floor mounting | - |
ErP | 2018 | - |
Series | Motor type | Heater type | Rated air flow [m³/h] | Service side | Control |
Blaubox: supply air unit | EC: electronically commutated motor | MW: water | 700; 1000; 1500; 2000; 3000; 4000 | L: left R: right |
S31 |
Model | Overall dimensions [mm] | |||||||||
H | H1 | H2 | L | L1 | L2 | W | W1 | W2 | W3 | |
Blaubox EC MW 2000 S31 | 440 | 300 | 318 | 900 | 770 | 65 | 700 | 754 | 847 | 500 |
HOW TO USE WATER HEATER DIAGRAMS | |
Air Speed. Starting from 1500 m³/h on the air flow scale draw a vertical line ➀ till the air speed axis which makes about 2.25 m/s.Supply air temperature. Prolong the line ➀ up to the point where it crosses the outside air temperature (blue curve), e.g. -5 °C; then draw a horizontal line ➁ from this point to the left till crossing water in/out temperature curve (70/50 °C). From this point draw a vertical line ➂ to the supply air temperature axis on top of the graphic (+38 °C). | Heating coil capacity. Prolong the line ➀ up to the point where it crosses the outside air temperature -15 °C (red curve) and draw a horizontal line ➃ from this point to the right until it crosses water in/out temperature curve (70/50 °C), from here draw a vertical line ➄ up to the scale representing the heating coil capacity (30 kW).Water flow. Prolong the line ➄ down to water flow axis at the bottom of the graphic ➅ (1750 kg/h).Water pressure drop. Draw the line ➆ from the point where line ➅ crosses the black curve to the pressure drop axis. (15 kPa). |