Mode | Voltage | Mounting | Casing material | EC motor | Maximum air flow | Frequency | RPM | Power | SEC class | Phase | Sound pressure level at 3 m | Heat exchanger type | Heat exchanger material | Electric heater power | Connected air duct diameter | Transported air temperature | Number of water coil rows | Insulation | Heat recovery efficiency | Voltage | Maximum air flow | Weight | ErP | Extract filter | Supply filter | Max. power without electric heater | Max. unit current without electric heater | Max. unit power with electric heater | Max. unit current with electric heater | Current | Electric heater current |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
KOMFORT EC DW 2000-2 R | 230 | ceiling mounting | aluzinc | yes | 1950 | 50/60 | 2920 | 840 | NRVU | 1 | 58 | cross-flow | aluminum | - | 315 | -25…+40 | 2 | 25 mm mineral wool | 75 | - | 542 | 194 | 2016 | G4 | G4 | - | - | - | - | 5.00 | - |
KOMFORT EC DE 2000-12 R | 400 | ceiling mounting | aluzinc | - | 2000 | 50/60 | 2920 | - | NRVU | 3 | 58 | cross-flow | aluminum | 12000 | 315 | -25…+40 | - | 25 mm mineral wool | 75 | - | 556 | 190 | 2016 | G4 | G4 | 840 | 5 | 12870 | 22.4 | - | 17.4 |
KOMFORT EC DE 4000-21 R | 400 | ceiling mounting | aluzinc | - | 4000 | 50/60 | 2580 | - | NRVU | 3 | 59 | cross-flow | aluminum | 21000 | 400 | -25…+40 | - | 25 mm mineral wool | 75 | - | 1111 | 290 | 2016 | G4 | G4 | 1980 | 3.4 | 23000 | 33.4 | - | 30.0 |